Step 5: (Gas Dryer Only) Connect Gas
Supply Pipe

1. Make certain your dryer is equipped for use with

the type of gas in your laundry room. Dryer is

equipped at the factory for Natural Gas with a

3/8 inch NPT gas connection.

NOTE: The gas service to a gas dryer must

conform with the local codes and ordinances, or in

the absence of local codes and ordinances, with the

latest edition of the National Fuel Gas Code ANSI

Z223.1/NFPA 54 or the CAN/CSA-B149.1 Natural

Gas and Propane Installation Code.

Natural Gas, 1000 Btu/ft

3

(37.3 MJ/m

3

) service must

be supplied at minimum 5.0 inch water column

pressure to maximum 10.5 inch water column

pressure.
For proper operation at altitudes above 3000 feet

(915 m) the natural gas valve spud orifice size must be

reduced to ensure complete combustion. Refer to

Table 1.

2. Remove the shipping cap from the gas

connection at the rear of the dryer. Make sure you

do not damage the pipe threads when removing

the cap.

3. Connect to gas supply pipe.

NOTE: When connecting to a gas line, an

equipment shut-off valve must be installed within

6 feet (1.8 m) of the dryer. An 1/8 in. NPT pipe plug

must be installed as shown for checking inlet

pressure. Refer to Figure 11.

To reduce the risk of gas leaks, fire or

explosion:

• The dryer must be connected to the type

of gas as shown on nameplate located in

the door recess.

• Use a new flexible stainless steel

connector.

• Use pipe joint compound insoluble in L.P.

(Liquefied Petroleum) Gas, or Teflon tape,

on all pipe threads.

• Purge air and sediment from gas supply

line before connecting it to the dryer.

Before tightening the connection, purge

remaining air from gas line to dryer until

odor of gas is detected. This step is

required to prevent gas valve

contamination.

• Do not use an open flame to check for gas

leaks. Use a non-corrosive leak detection

fluid.

• Any disassembly requiring the use of

tools must be performed by a suitably

qualified service person.

W316

WARNING

Natural Gas Altitude Adjustments

Altitude

Orifice Size

Part No.

feet

m

No.

inches

mm

3000

915

43

0.0890

2.26

503778

6000

1830

44

0.0860

2.18

58719

8000

2440

45

0.0820

2.08

503779

9000

2740

46

0.0810

2.06

503780

10,000

3050

47

0.0785

1.99

503781

Table 1

D434I

1

New stainless steel flexible connector -
(Use design CSA certified connector)
Use only if allowed by local codes

2

1/8 in. NPT Pipe Plug

3

Equipment Shut-Off Valve

4

Black Iron Pipe
Shorter than 20 ft. (6.1 m) -
Use 3/8 in. (9.5 mm) pipe
Longer than 20 ft. (6.1 m) -
Use 1/2 in. (12.7 mm) pipe

5

3/8 in. NPT Gas Connection

Figure 11

1

3

2

4

5