The controls which are frequently used in the normal operation of the instrument are
all accessible on the control panel. Some switches, which are infrequently used,
are located on the back of the main circuit board.

4.7.2

The DIP switches are scanned only on power-up and every time the instrument is
taken out of the menu mode. Therefore, after changes to the DIP switch settings,
you must bring up the menu by pressing CALL, and then return the instrument to
the online mode by pressing RUN, in order for the instrument to scan the new DIP
values.


4.7.3

The following table describes the use of the 16 DIP switches:

Bank S1

Dip Switch Description

ON

OFF

1

Selects temperature unit

°C

°F

2

Password Feature

Disabled

Enabled

3

Fail-Safe mode for Relay A

Enabled

Disabled

4

Direction of Control for Relay A

Falling

Rising

5

Alarm Relay to be activated for memory loss

Disabled

Enabled

6

Fail-Safe mode for Alarm Relay

Enabled

Disabled

7

Auto return from menu

Enabled

Disabled

8

0-5V / 0-1mA Select

Conductivity Temperature


Bank S2

Dip Switch Description

ON

OFF

1

Cycling Control for Relay A

Enabled

Disabled

2

Reserved

3

Reserved

4

Reserved

5

Reserved

6

Reserved

7

Reserved

8

Reserved


Note: Items in “BOLD” are the factory settings that the unit will be shipped with.