RT-Ex15 Display Modes

The RT-Ex15 has ten display/program modes:

LOGO

GR

TOTAL

A* RAT

A

TOT

A*

RATE A

GT

STATUS ONE*

BATCH TOTAL

RATE A

PL

ANALOG OUT

TOTAL

A

LIMITS

*Display only, no programming function


During normal operation with the cover secured, the Display Mode is changed by touching the
side of the magnet wand to the MODE/DN location (top) on the outside of the housing. The
MODE/DN button is used to change the Display Mode when the RT-Ex15 cover is opened
during programming. The RT-Ex15 will retain the last display mode selected and display it on
power up. Seven of the display modes are also used to program the related variables.

LOGO Mode - Turning On/Off Displays

LOGO – Display Mode “RT-Ex15” is used during unit programming/set-up to turn-on or turn-
off Display Modes. Not every user will require all of the display modes and any of the ten
Display Modes can be turned off based on a user’s particular needs. To reassign, turn-on, or turn-
off a display mode, use the MODE/DN button or magnetic switch to select the LOGO display
mode. Press and hold the ENT button or activate and maintain the ENT magnetic switch. The
display will first show a P in the lower left-hand corner and then show DISPLAY 00 and indicate
which display mode is assigned to DISPLAY 00. DISPLAY 00 is assigned to the LOGO screen
allowing access for display activation/deactivation.

NOTE: It is highly recommended that displays to be turned off are done one at a time returning
to LOGO display after each screen is turned off. Always turn off the highest numbered
displays first.

To turn-off a display mode, use the ENT button or magnetic switch to scroll through the
DISPLAY #s until the appropriate display mode is encountered. Use the RESET/UP button or
magnetic switch to turn the display off. The DISPLAY # assignment will indicate OFF DISPL.
Use the ENT button or magnetic switch to store the current assignment and advance the RT-
Ex15 to the next available display number (00-09) or exit the LOGO display programming
procedure.

To change a DISPLAY # assignment to a different mode use the SEL button or magnetic switch
to select from the available display modes. Any DISPLAY # can be assigned as any display
mode. Use the ENT button or magnetic switch to store the current assignment and advance the
RT-Ex15 to the next available display number (00-09) or exit the LOGO display programming
procedure.

To restore a Display Mode that has been turned off, use the ENT button or magnetic switch to
select a DISPLAY # with a OFF DSPL assignment. Select a display mode assignment using the
SEL button or magnetic switch. Use the ENT button or magnetic switch to store the current
assignment and advance the RT-Ex15 to the next available display number (00-09) or exit the
LOGO display programming procedure.