Operation and Programming Manual

21


DELAY

This variable sets the delay time for Relay2 (high flow solenoid output) relative to the START input.
Typical delays are from 0.00 to 4.00 seconds. This function is used in slow start applications where
Relay1 (low flow solenoid output) is energized immediately at a START input and Relay2 (high flow
solenoid output) is turned on after the DELAY time.

00000.50 seconds

Press and hold UP or DN to increase or decrease the value.

To increase the increment or decrement rate:

for medium, press and hold SEL while holding UP or DN

for maximum, press and hold ENT while holding UP or DN

When the value displays, press the ENT to store it and advance to the next variable.

Always release SEL or ENT before releasing UP or DN, or the LLC-BA will proceed to the next variable
leaving the last variable with an unpredictable value.

PRECUT

This variable sets the batch quantity remaining when Relay2 (high flow solenoid output) is turned off.
Program using the KFT engineering units and decimal point. This function is used in slow stop
applications where Relay2 (high flow solenoid output) is turned off at a PRECUT amount before the total
batch quantity is reached and Relay1 (low flow solenoid output) remains energized until the batch
quantity is reached.

0000000 pulses

Press and hold UP or DN to increase or decrease the value. To increase the increase or decrease rate,
while holding the UP or DN, press and hold the SEL for medium rate or ENT for maximum rate. When the
desired value is displayed, press ENT to store the programmed value and advance to the next variable.

Always release SEL or ENT before releasing UP or DN, or the LLC-BA will proceed to the next variable
leaving the last variable with an unpredictable value.

Gate Time

This variable sets the sampling time for display of the incoming frequency. You will program it in
complete seconds and the allowable range is from 1 to 30 seconds. The variable only affects the update
of the display and is useful in stabilizing the display when dealing with variations in flow. In low rate