COSA Xentaur COSA 9610 User Manual

Page 17

Advertising
background image

INSTALLATION, OPERATION AND MAINTENANCE MANUAL – COSA 9610™

Page 17 of 44

Signal cables
The COSA 9610™ has multiple input and output signals, which can be split in two groups,

analog and digital signals. Both analog and digital signals are to be connected in the

electronics enclosure. Please make sure that the cable glands used are suitably certified.

For details see project specific drawings. Control equipment connected to barrier must not

use or generate more than 250Vrms or 250Vdc.

Analog signals
The COSA 9610™ has two 4-20mA analog outputs (4 optional). The signals can be user-

programmed to represent various measurement readings, such as Wobbe index and CARI

index. The analog output signals are wired via isolating barriers. Please note that these

barriers are to be connected to an intrinsic safe earth (I/S). When no intrinsic safe earth

is available the barriers may be connected to a potential free earth (PE) with a resistance

of less than 1 ohm. For details see project specific drawings.

Digital signals
The digital signals are divided in three, Digital outputs (alarm/status), digital input, and

RS-485 serial signals. For details see project specific drawings.

Advertising