Specifications

Voltage

8.5 – 33 VDC, non polarity sensitive

Maximum ripple (pk to pk)

10% (V

p - p

)

Typical average standby current (24V)

731U, 741UT

100µA

711U, 711UT, 721UT

70µA

Typical alarm current (24V) -2 Wire

up to 60 mA (max), if not limited by control panel

Typical alarm current (24V) -4 Wire

up to 50mA (max) but 15mA (min)

Relay contacts

2 A @ 30 VDC, 1 A @ 120 VAC

Sensitivity

2.85%, + 0.37, – 0.75%

Operating temperature

32°F to 120°F (0° to 49°C)

Operating humidity range

0 to 95% Non-condensing

RFI Immunity

20 V/m minimum; 0-1000 MHz

Color

White head and base

Field wiring size

12-24 AWG

Heat detector specifications

Fixed temperature - 135°F ± 3°F (57°C ± 1.7°C)

(for 711UT, 721UT, and 741UT)

Rate of rise - 15°F/min and > 105°F (8.3°C/min and > 40.6°C), 50 ft. spacing for 711UT/721UT/741UT

UL two-wire compatibility identifier

S10A for all models except 731U/731L, S11A for 731U/731L, S00 for all bases

Remote LED output current

5 mA min, 8.5 mA max

Drift compensation adjustment

1.0%/ft. max for photoelectric models

0.5%/ft. max for ionization models

Detector head dimensions

4" (10 cm) diameter; 1.75" (4.44 cm) height

Base dimensions

702E

4" (10 cm) diameter; 0.05" (1.27 cm) height

701U, 702U

6" (15.2 cm) diameter, 0.6" (1.3 cm) height

Total height, head and base together

1.98" (5 cm) height

Remote test input

100 ohm max

Reset voltage

2.5V max

Reset time

1 second minimum

Listings

UL 268, FM, MEA, CSFM

Product Ordering

Detectors

Description

711U

2-wire photoelectric type smoke detector

711UT

2-wire photoelectric type smoke detector with rate-of-rise heat detector and fast response algorithms

721UT

2-wire photoelectric type, with rate-of-rise heat detector with fast response algorithms, remote test, alarm/trouble LED output

731U

2-wire photoelectric type smoke detector, with auxiliary relay (N.C./N.O.) outputs, UL Listed for releasing service

741UT

4-wire photoelectric type smoke detector, alarm relay (N.O.) output and remote alarm/trouble LED output with rate-of-rise heat

detector with fast response algorithms

731L

(OEM only, not for resale) See 731U description

B a s e s

701U

Base, for 711U heads; 6" (15 cm) base, 3 terminal connectors

702E

Base, for all heads; 4" (10 cm) base, 6 terminal connectors

702U

Base, for all heads; 6" (15 cm) base, 6 terminal connectors

702RE

Base, for 731U relay type smoke detector heads; 4" (10 cm) base, 6 terminal connectors

702RU

Base, for 731U relay type smoke detector heads; 6" (15 cm) base, 6 terminal connectors

Accessories

204-12/24V

End-of-line, power supervision relay for 4-wire applications

SM-200

Smoke! in a can

®

(canned smoke) for functional testing of smoke detectors

211

Replacement optical block cover for all models (set of 10)

706U1A

Remote Indicator with red alarm LED, for use with 731U and 741UT

706U2A

Remote Indicator with red alarm LED and keyed remote test, for use with 731U and 741UT

706U3A

Remote Indicator with red alarm LED, keyed remote test and reset, for use with 731U and 741UT