Specifications

Voltage

Refer to Table 2 and Table 3

Current

Refer to Table 2 and Table 3

Dimensions

Refer to Table 4 on page 6

Weight

9 lb (4.1 kg)

Hazardous locations
Ambient

temp.

-31 to 104°F (-35 to +40°C)

Non-hazardous
locations
Variable

ambient

temp

-40 to 151°F (-40 to +66°C)

Table 1: Operating temperature codes

Catalog number

Class I, Div. 2
Groups A, B, C, D

Class II, Div. 2,
Groups F, G

Class III, Div. 1 and
2

5531M-24AQ
5531M-24N5
5531M-120N5*
5531MHV-24AQ
5531MV-24N5
5531MV-120N5*

135°C (T4)

100°C (T5)

5531M-24Y6
5531M-120Y6*
5531MHV-24Y6
5531MHV-120Y6*
5531MV-24Y6

180°C (T3A)

100°C (T5)

Table 2: Input board

Catalog number

Voltage

Current

5531M-24AQ
5531M-24N5
5531M-24Y6
5531MHV-24AQ
5531MHV-24Y6
5531MV-24N5
5531MV-24Y6

24 VDC

6 mA

5531M-120N5
5531M-120Y6
5531MHV-120Y6
5531MV-120N5

120V 50/60 Hz

13 mA

Table 3: Main power

Catalog number

Voltage

Standby
current

Tone on
current

5531M-24AQ

24 VDC
24 VAC 50/60 Hz

0.10 A
0.10 A

0.74 A
1.3 A

5531M-24N5
5531MV-24N5

120 VAC 50/60 Hz

0.10 A

0.36 A

5531M-24Y6

5531MV-24Y6

125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz

0.10 A
0.02 A
0.10 A
0.10 A

0.21 A
0.10 A
0.32 A
0.20 A

5531M-120N5
5531MV-120N5

120 VAC 50/60 Hz

0.10

0.38 A

5531M-120Y6

125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz

0.10 A
0.02 A
0.10 A
0.10 A

0.20 A
0.10 A
0.31 A
0.20 A