P/N 3100008 • REV 4 • ISS 09AUG10

7 / 8

Tone

SW 4-6 SW 4-5 SW 4-4 SW 4-3 SW

4-2 SW4-1 Description

Hex

RESERVED

OFF ON OFF ON ON

ON RESERVED

17

RESERVED

OFF ON ON OFF OFF

OFF RESERVED

18

RESERVED

OFF ON ON OFF OFF

ON RESERVED

19

RESERVED

OFF ON ON OFF ON

OFF RESERVED

1A

NFPA Whoop

OFF

ON

ON

OFF

ON

ON

Three 422 – 775 Hz upward sweeps, 850 ms each, 1 s
delay and repeat

1B

3 Pulse Horn*

OFF

ON

ON

ON

OFF

OFF

470 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat

1C

3 Pulse Air Horn*

OFF

ON

ON

ON

OFF

ON

370 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat

1D

3 Pulse Dual
Tone*

OFF

ON

ON

ON

ON

OFF

450 – 500 Hz, 0.4 to 0.5 s cycle, 3 0.5s pulses
separated by 0.5 s followed by 1.5 s delay and repeat

1E

3 Pulse Chime 2*

OFF

ON

ON

ON

ON

ON

575 Hz, 3 0.5 s pulses separated by 0.5 s followed by
1.5 s delay and repeat

1F

European

Police ON OFF OFF OFF OFF

OFF 969

Hz and 800 Hz alternately 0.250 s each

20

European Fire

ON

OFF

OFF

OFF

OFF

ON

982 Hz and 864 Hz downward sweep in 0.134 s

21

European Slow
Whoop

ON

OFF

OFF

OFF

ON

OFF

658 – 1312 Hz upward sweep in 3 s followed by 0.5 s
delay and repeat

22

European General

ON

OFF

OFF

OFF

ON

ON

1087 Hz for 0.5 s followed by 0.5 s delay and repeat

23

European Toxic

ON

OFF

OFF

ON

OFF

OFF

982 Hz continuous

24

European Police 2

ON

OFF

OFF

ON

OFF

ON

554 Hz and 440 Hz alternately, 0.8 s each

25

European Stutter

ON

OFF

OFF

ON

ON

OFF

3876 Hz for 0.146 s followed by 0.102 s delay and
repeat

26

European Sweep

ON

OFF

OFF

ON

ON

ON

1315 Hz – 413 Hz downward sweep in 1.17 s and
repeat

27

Telephone

2

ON OFF ON OFF OFF

OFF Alternate tones at 567 Hz and 326 Hz

28

Buzzer

ON OFF ON OFF OFF

ON 1315

Hz

and

746 Hz alternating for 0.003 s each

29

Genesis Horn Cont

ON

OFF

ON

OFF

ON

OFF

Continuous Genesis horn

2A

Genesis Horn
Temp

ON OFF ON OFF ON

ON Temporal

Genesis

horn

2B

Warning

1

ON OFF ON ON OFF

OFF 1207

Hz and 493 Hz, alternately 0.002 s each

2C

Warning

2

ON OFF ON ON OFF

ON 2336

Hz and 493 Hz, alternately 0.005 s each

2D

Warning 2 Beep

ON

OFF

ON

ON

ON

OFF

0.500 s of 2336 Hz and 493 Hz each alternating for
0.005 s followed by 1 s delay

2E

Caution

ON

OFF

ON

ON

ON

ON

453 Hz for 0.040 s, 235 Hz for 0.020 s, 235 Hz for 0.160
s, 260 Hz for 0.050 s, 260 Hz for 0.1009 s, 235 Hz for
0.050 s

2F

Multi-tone

ON

ON

OFF

OFF

OFF

OFF

376, 357, 352, 382, 355, 375, 384, 375 and 364 Hz
alternately on for 0.050 s

30

Attention

ON

ON

OFF

OFF

OFF

ON

2232, 4545, 3704, 2777, 4347, 3704, 2500 Hz
alternately on for 0.003 s

31

High Freq. Steady
Alert

ON ON OFF OFF ON OFF 2500

Hz

continuous

32

High Freq. Fast
Siren

ON

ON

OFF

OFF

ON

ON

2500 – 3048 Hz up and down sweep in 0.130 s

33

High Freq. Slow
Siren

ON

ON

OFF

ON

OFF

OFF

2500 – 3048 Hz up and down sweep in 0.500 s

34

DIN PFEER

ON

ON

OFF

ON

OFF

ON

Ramp downward from 1336 Hz to 522 Hz in 1.2 s and
repeat

35

NF S 32 001

ON

ON

OFF

ON

ON

OFF

584 Hz for 0.100 s and 461 Hz for 0.400 s

36

Ode to Joy

ON

ON

OFF

ON

ON

ON

6.45 s of melody followed by 1 s delay and repeat

37

Twinkle Little Star

ON

ON

ON

OFF

OFF

OFF

13.2 s of melody followed by 1 s delay and repeat

38

Dueling Banjos

ON

ON

ON

OFF

OFF

ON

10.84 s of melody followed by 1 s delay and repeat

39

La Cucaracha

ON

ON

ON

OFF

ON

OFF

7.10 s of melody followed by 1 s delay and repeat

3A

Yellow Rose of TX

ON

ON

ON

OFF

ON

ON

19.34 s of melody followed by 1 s delay and repeat

3B

*3 Pulse Tones are for Evacuation Use Only

CAUTION: The use of evacuation signals on this product, that is not specifically listed for fire alarm use, is subject to the approval
of the authority having jurisdiction.