P/N 3100008 • REV 4 • ISS 09AUG10

Catalog number

Voltage

Standby
current

Tone on
current

5531MHV-24AQ

24 VDC
24 VAC 50/60 Hz

0.10 A
0.10 A

1.5 A
2.3 A

5531MHV-24Y6

125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz

0.10 A
0.02 A
0.10 A
0.10 A

0.39 A
0.19 A
0.56 A
0.34 A

5531MHV-120Y6

125 VDC
250 VDC
120 VAC 50/60 Hz
240 VAC 50/60 Hz

0.10 A
0.02 A
0.10 A
0.10 A

0.40 A
0.20 A
0.62 A
0.37 A

Table 4: Dimensions

5531M

5531MHV

A

8 7/8” (225 mm)

11 1/2” (292 mm)

B

8 1/4” (210 mm)

9 3/4” (248 mm)

C

13” (330 mm)

14 1/4” (362 mm)

Table 5: PLC compatibility: PLC output to meet following product input parameters. Refer to Figure 9 and Figure 12.

Catalog number

Operating voltage

Max. off state leakage

current

Continuous on current

Surge (inrush/duration)

5531M-24AQ

24 VDC only

2 mA

740 mA

8 A / 4 mS

5531M-24N5
5531MV-24N5

120 VAC 50/60 Hz

2 mA

360 mA

2.82 A / 4 mS

5531M-120N5
5531MV-120N5

120 VAC 50/60 Hz

5 mA

380 mA

2.82 A / 4 mS

5531MHV-24AQ

24 VDC only

2 mA

1500 mA

8 A / 4 mS

Input board circuit

24 VDC

2 mA

6 mA

--

Input board circuit

120 VAC 50/60 Hz

5 mA

13 mA

--

Table 6: Tone programming

Tone

SW 4-6 SW 4-5 SW 4-4 SW 4-3 SW

4-2 SW4-1 Description

Hex

No

Tone

OFF OFF OFF OFF OFF

OFF

00

Ding-Dong

OFF OFF OFF OFF OFF

ON Percussive pairs of 700 and 570 Hz tones, each

damped to 0

01

Warble

OFF

OFF

OFF

OFF

ON

OFF

575 and 770 Hz alternately, 87 ms each

02

Siren

OFF

OFF

OFF

OFF

ON

ON

600 – 1250 Hz up and down sweep in 8 s and repeat

03

Stutter

OFF OFF OFF ON OFF

OFF Percussive 470 Hz, 83 ms on, 109 ms off

04

Slow Whoop

OFF

OFF

OFF

ON

OFF

ON

600 – 1250 Hz upward sweep in 4 s and repeat

05

Beep

OFF

OFF

OFF

ON

ON

OFF

470 Hz, 0.55 s on, 0.55 s off

06

Chime 1

OFF

OFF

OFF

ON

ON

ON

700 Hz percussive repeat at 1 Hz

07

Fast Whoop

OFF

OFF

ON

OFF

OFF

OFF

600 – 1250 Hz upward in 1 s and repeat

08

Hi/Lo

OFF

OFF

ON

OFF

OFF

ON

780 to 600 Hz alternately, 0.52 s each

09

Rapid Siren

OFF

OFF

ON

OFF

ON

OFF

600 – 1250 Hz up and down sweep in 0.25 s and repeat

0A

Yeow

OFF

OFF

ON

OFF

ON

ON

1250 – 600 Hz downward sweep in 1.6 s and repeat

0B

Horn OFF

OFF

ON

ON

OFF

OFF

470 Hz continuous

0C

Air Horn

OFF

OFF

ON

ON

OFF

ON

370 Hz continuous

0D

Dual Tone

OFF

OFF

ON

ON

ON

OFF

470 – 500 Hz, 0.4 to 0.5 s cycle

0E

Chime 2

OFF

OFF

ON

ON

ON

ON

575 Hz percussive repeat at 1 Hz

0F

Westminster

OFF ON OFF OFF OFF

OFF Two

measures, 411 Hz, 520 Hz, 407 Hz, 312 Hz

10

Three Blind Mice

OFF

ON

OFF

OFF

OFF

ON

Four measures, 787 Hz, 714 Hz, 625 Hz, 952 Hz, 333
Hz

11

Phasor

OFF

ON

OFF

OFF

ON

OFF

416 – 625 Hz up and down sweep in 13 ms and repeat

12

Telephone

OFF

ON

OFF

OFF

ON

ON

570 and 770 Hz alternately, 50 ms each for 1.2s, 1.5s
delay and repeat

13

Staircase

OFF ON OFF ON OFF

OFF 440

2000 Hz up and down steps, 750 ms delay and

repeat

14

3 Tone Alert

OFF

ON

OFF

ON

OFF

ON

463 Hz, 641 Hz, and 896 Hz, 200 ms each, 1 s delay
and repeat

15

RESERVED

OFF ON OFF ON ON

OFF RESERVED

16