3.12 - Standby Power Mode

The panel can be programmed to accept standby power from
an Edwards EBPS10 auxiliary power supply or other UL regu-
lated standby power source listed for fire. When this feature
is enabled, the standby power input is continuously moni-
tored for integrity. When disabled, the standby power input is
only monitored when the panel has detected the loss of AC
main power.

NOTE: When the System Master is used with a fire alarm

panel, Standby Power MUST be installed and
enabled.

1.

From the LCD screen, press the

button until LCD

displays:

Standby Power Mode
Mode: DISABLED

2.

Press the

button to enable/disable the standby power mode.

3.13 - Remote Programming

Millennium System Master panels can be programmed remotely
using Edwards System Master programmer P/N XXXXXX. Enabling
program mode to 'ready' begins to upload and download the se-
quence to the programmer. Once programming is complete, mode
will change back to disabled.

3.14 - Text Output String

Millennium System Master Panel is capable of interfacing to Edwards
Message Center signs. Key inputs 1-4 can be programmed to recall
message sign file labels A-Z. Up to two file labels can be assigned to
each of the four key inputs. Each input can also address individual
signs between addresses 00 and FF.

Text Output String Format is as follows:

The panel will be inoperative until the program sequence is com-
pleted and the panel has timed out of setup mode.

Example: Text Output String

3.15 - Security

The panel programming can be secured after programming is com-
plete. Using the keys supplied with the console, turn the lock on
the inside door (below the LCD panel) until it stops. In this posi-
tion, all alarm and paging inputs can be activated but the function
key is disabled.