Installation and Configuration

Mounting the Charger

12

CHG-75 PN 51315:A 08/01/01

2.3.4 Ground Fault Detection Disable

Cut jumper JP2 to disable reporting of a local ground fault condition. The charger’s
ground fault detection circuit might be disabled when the charger is connected to
equipment with its own ground fault detection circuit to prevent competition between
the two circuits. Note that Ground Fault detection is required in Canada. Refer to
Figure 2.1 on page 10, for location of the jumper.

2.3.5 AM-1 Ammeter Enable

Cut jumper JP5 to enable the operation of the AM-1 Ammeter when installed on the
CHG-75 charger. Refer to Figure 2.1 on page 10, for location of the jumper.

2.4 Mounting the Charger

2.4.1 Mounting the Charger in an FACP

The CHG-75 can be mounted in the bottom of the MS-9600 backbox, using the self-
tapping screws included with the charger. In a similar fashion, the supplied nuts can be
used to mount the charger to pem studs located in the bottom of the MS-9200 backbox.
A separate battery box must be used to house the batteries when employing these
configurations. Figure 2.3 illustrates the CHG-75 mounting location in the MS-9600.
The pem studs are located in the same area in the MS-9200 backbox .
Note: The CHG-75 must be mounted in the same room and within 20 feet of the FACP.

+ BAT TE R Y -

LC D D IS PL AY

K EY PA D I/F

S ECU RIT Y O PT BD

O P T D A C T

H O T

CB1

J3

J12

J2

TB1

TB2

TB3

JP3

JP2

SW1

JP5

JP6

J17

J16

J6

J8

J7

J10

J11

C U T T O
D ISA B LE
LO CA L
C H AR G ER

D ISA B LE
G N D
F LT

C U T T O
M O N ITO R 4X T M

O P T S LC

4X T M O P T B D

TB4

TB5

TB6

TB7

TB8

N E U T E ART H

Figure 2.3 MS-9600 Backbox

mounting holes for CHG-75

MS-9600 FACP

9600powr

.cdr

Advertising