SECTION 1

Product Description

The CHG-75 battery charger is designed to charge lead-acid batteries that provide
emergency standby power for an FACP (Fire Alarm Control Panel) and related
equipment. Two 12 volt batteries are used in series to supply a nominal 24VDC. The
battery charger is compatible with any FACP that uses lead-acid batteries with a rating
of 25 AH (Amp Hours) to 75 AH. The FACP must have a feature that allows the
disabling of the control panel battery charger.

The CHG-75 can be configured for 120 VAC operation or 220/240 VAC operation via
jumper selection.

1.1 Features

120 VAC or 220/240 VAC operation via JP1 jumper selection

Charger capacity of 25 AH to 75 AH

Mounts in a BB-26, BB-55F, MS-9600 and MS-9200 enclosure

Screw terminal connection for battery

F2, 15 amp replaceable fuse provides battery current-limiting, short circuit and
overload protection

Screw terminal connection for battery backup to other equipment

F3, 15 amp replaceable fuse provides current-limiting and overload protection
for output to connected equipment

Fail-safe Form-C trouble relay rated for 2 amps @ 30 VDC (resistive)

Ground fault detection circuit which can be disabled by cutting jumper JP2

Battery and charger voltage supervision

AC voltage supervision

AC loss reporting delay option, jumper selectable for 8 or 16 hour delay

Connectors for trouble input and trouble output which direct CHG-75 troubles to
FACP and allows daisy-chaining of external troubles through the charger without
affecting charger operation

Master trouble input allows monitoring of another device or zone

Connectors for optional AM-1 ammeter and VM-1 voltmeter

LEDs for monitoring charger condition

Screw terminal connection for SLC loop

Direct SLC interface for charger trouble and/or AC loss reporting to the FACP