Out - out + cut jp3 for this application – Fire-Lite CHG-75 Battery Charger User Manual

Page 21

Advertising
background image

Connecting the Charger to a Load

Installation and Configuration

CHG-75 PN 51315:A 08/01/01

21

2.9.3 Connecting the Charger to an MS-9600

The charger can be connected to an FACP power supply, such as an MS-9600, by
disabling the local charger. The MS-9600 charger is disabled by cutting jumper JP3.

To connect a charger to the MS-9600:

1. Disconnect all power (AC and DC) from the MS-9600 and CHG-75

2. Cut jumper JP3, which is located on the MS-9600 main circuit board, to disable

the FACP battery charger

3. Connect the CHG-75 Output Circuit TB2, Terminal 3 (Out +) to MS-9600

battery connector TB2 (+) terminal and Terminal 4 (Out -) to MS-9600 battery
connector TB2 (-) terminal as illustrated in Figure 2.13. Be certain to observe
proper polarity.

4. Connect the batteries to the charger (refer to Figure 2.10 and Figure 2.11).

+

-

B AT T E RY

LCD D IS PL AY

K EY PA D I/F

S ECU RIT Y O PT BD

1
2
3

O P T D A CT

HO T

CB1

J3

J12

J2

TB1

TB2

TB3

JP3

JP2

JP8

JP4

JP7

JP5

JP6

JP6

J17

J16

J6

J8

J7

JP10

JP11

CU T T O
DISA B LE
LO CA L
CH ARG ER

DISA B LE
G N D
F LT

CU T T O
M O NITO R 4X T M

O P T S LC

4X T M O P T B D

TB4

TB5

TB6

TB7

TB8

NE U T E ART H

1

4

*

2

5

0

3

6

#

1

s t

EV ENT

AB C

D EF

G H I

J K L

M N O

PR S

T U V

W X Y

Q Z

-/.

C LR

7

8

9

E S C

ENTER

RECALL

ACK/ST EP

SILENCE

DRILL

HOLD 2 S EC

RESET

M O DE

MAINTENANCE

SILENCED

DISABL ED

BATTERY

GROUND

TROUBLE

SUPERVISORY

FIRE ALARM

AC POWER

-

+

-

+

J P 1

J P 3

S W 1

J P 4

T B 3

T B 4

T B 2

ENAB LE
AC D EL AY

16 HR
DE LAY

TE NS

O NE S

CU T F OR
240V AC

G ND FLT
DI SA BL E

AM-1 ENAB LE

ADDR ES S

O N

O FF

AM-1

J P 5

J P 2

F 1

F 2

J 4

J 1

J 2

J 3

F 3

T B 1

HO

T

OU

T

+

BA
T

+

OU

T

-

BA
T

-

EA
R

T

H

NE
UT

15

15

A- B- A + B +

NC NO C

0

4 3

9

2

6

1

5 7

8

12

13

15

14

10

11

0

4 3

9

2

6

1

5 7

8

12

13

15

14

10

11

Figure 2.14 CHG-75 Wiring to MS-9600

Battery -

Battery +

+

+

-

-

+

-

Battery

Interconnect

Cable*

MS-9600

CHG-75

75 AH
12V

75 AH
12V

AC Power

Hot

Neutral

Earth

Out -

Out +

Cut JP3 for this application

c

hg79600

.c

dr

Advertising