12

ECC-50/125DA Instruction Manual — P/N LS10027-000FL-E:B 8/13/2013

ECC-50DA Remote Amplifier

Installation

1.1.7 Connecting AC Power

To install the AC transformer into the ECC-50DA cabinet, follow these steps:

1. Open the cabinet door.
2. To access cabinet interior, open the dress panel by removing the upper screw and the mid-door

retaining screw.

3. Mount the transformer onto the threaded cabinet transformer mounting studs using the

supplied locking hex nuts as shown in Figure 1.9.

Module

Voltage

Transformer

P/N

Standby

Current

Alarm Current

ECC-50DA 25V

120 VAC, 60 Hz

115061

350 mA

1100 mA

ECC-50DAE 25V

230 VAC, 50 Hz

115031

200 mA

600 mA

ECC-50DA 70V

120 VAC, 60 Hz

115061

350 mA

1200 mA

ECC-50DAE 70V

230 VAC, 50 Hz

115031

200 mA

600 mA

Table 1.2 ECC-50DA AC Current Draw