2.1.7 Connecting AC Power

At installation, connect the AC terminals to the power source as shown in Figure 2.10. It may be
necessary for a professional electrician to make this connection.

Module

Voltage

Standby

Current

Alarm Current

ECC-125DA

120 VAC, 60 Hz

300 mA

2200 mA

ECC-125DAE

240 VAC, 50 Hz

250 mA

1250 mA

Figure 2.9 ECC-125DA AC Current Draw