2.1.9 Calculating Current Draw and Standby Battery

This section helps you determine the current draw and standby battery needs for your installation
(18 Ampere Hours maximum will fit in cabinet). Complete the remaining instructions in Table 2.2.

For batteries larger than 18 AH, use the BB-26 or BB-55FBattery Box. A maximum of 35 Ampere
Hours is allowed per system.

Device

No. of

Devices

Current Per Device

Standby

Current

Alarm

Current

ECC-125DA

1

Standby: 375 mA

375 mA

Alarm: 700 mA

700 mA

ECC-CE4

0 or 1

Standby: 20 mA

Alarm (All Channels): 180 mA

mA

A

Current Subtotals:

mA

mA

Notification Devices

Refer to device manual for number of devices and current ratings.

B

Current Subtotals:

mA

mA

C Total current rating of all devices in system (Line B) X .001

A

A

D Number of standby hours (24 or 60 for NFPA 72)

H

E Multiply line C (standby current) and D: Total standby AH

AH

F Alarm sounding period in hours (For example, 5 minutes = .0833 hours):

H

G Multiply line C (alarm current) and F: Total alarm AH

AH

H Add lines E and G (AH = Ampere Hours): Total AH required

AH

Table 2.2 Current Draw Calculations

Advertising