Figure 3-1: power connection, Led-10 series – Fire-Lite LED-10 Series Remote Fire Annunciator User Manual

Page 16

Advertising
background image

16

Document 50400 Rev B 10/27/97 P/N 50400:B

Section Three: LED-10 Series Electrical Connections

The LED-10 Series Annunciators can be powered by the MS-5210UD power output or
from a remote, UL listed, filtered power supply such as the Fire•Lite FCPS-24F. The
power run to the LED-10 Series must be power-limited but need not contain a power
supervision relay since loss of power is inherently supervised through loss of communi-
cation with the annunciator. Maximum LED-10 Series current draw from the power
supply under alarm condition is 28 mA. Maximum current draw from the control panel's
secondary power source (batteries) under loss of AC power is 24 mA.

Note: All connections are power-limited and supervised.

Figure 3-1: Power Connection

n/c

Plug-in terminal blocks

Earth Ground Option

LED-10 Series

+ 24 VDC

- 24 VDC

+ 24 VDC

- 24 VDC

To next annunciator or ACM-8RF

From Main Power Supply