Figure 1-2: wiring to terminals – Fire-Lite LED-10 Series Remote Fire Annunciator User Manual

Page 6

Advertising
background image

6

Document 50400 Rev B 10/27/97 P/N 50400:B

Figure 1-2: Wiring to Terminals

Current Consumption @ 24 VDC nominal (filtered)
Normal/Standby (no activity): 23 mA
Trouble Condition: 31 mA
Alarm: 28 mA (1 zone in alarm)
40 mA (all 10 zones in alarm)
AC Fail: 24 mA

Note: These connections must be power-limited and the +24 volt nominal power (18 VDC to 26 VDC)
must be filtered.

Earth Ground Option

-24 VDC OUT

-24 VDC IN

+24 VDC OUT

+24 VDC IN

No connection

+EIA-485
-EIA-485
Shield
No connection

Side view

(rotated 180

o

from above
[Top] view)

Advertising