Figure 1-2: wiring to terminals – Fire-Lite LED-10 Series Remote Fire Annunciator User Manual
Page 6
Advertising
6
Document 50400 Rev B 10/27/97 P/N 50400:B
Figure 1-2: Wiring to Terminals
Current Consumption @ 24 VDC nominal (filtered)
Normal/Standby (no activity): 23 mA
Trouble Condition: 31 mA
Alarm: 28 mA (1 zone in alarm)
40 mA (all 10 zones in alarm)
AC Fail: 24 mA
Note: These connections must be power-limited and the +24 volt nominal power (18 VDC to 26 VDC)
must be filtered.
Earth Ground Option
-24 VDC OUT
-24 VDC IN
+24 VDC OUT
+24 VDC IN
No connection
+EIA-485
-EIA-485
Shield
No connection
Side view
(rotated 180
o
from above
[Top] view)