SilentKnight VisorAlarm Plus 2U User Manual

Page 20

Advertising
background image

With this option the receiver does not apply any filters and displays all the stored signals
beginning with the most recent.

Each signal is displayed as in the next figure:

16:33:23 00001234
E110 01 001 Fire

The list can be navigated using the e and f keys. Use the left arrow to go to a newer signal
and the right one to go to an older one.

If the OK key is pressed while one signal is being displayed, extended info for that signal is
shown on the display:

By pressing OK again the previous view is recovered.

2. Search only the System Troubles.

System troubles are unrestored trouble signals generated by the receiver itself. The signals
generated by the VisorALARM PLUS 2U receiver always have the 00000000 account code
that is reserved and cannot be assigned to a mIP/IPDACT device.

The set of trouble signals that VisorALARM PLUS 2U can raise is described in the next table:

Trouble signal

Description

Hdw failure: Fan 0

Fan #0 has failed

Hdw failure: Fan 1

Fan #1 has failed

Hdw failure: LCD

Failure in the LCD device

Hdw failure: Buzzer

Failure in the Local Piezo Sounder

Hdw failure: Printer

Printer not detected

Network failure

The device specified in the monitor_ip_address

configuration parameter does not answer.

Probably the internet link is down

Receiver is down

The receiver cannot receive signals

Primary is down

The Backup receiver has detected that the Primary

receiver is down

Backup is down

The Primary receiver has detected that the Backup

receiver is down

Storage full

Received signals queue is full

Time is inaccurate

The NTP server specified in the NTP configuration

does not answer.

The synchronization of the Primary and Backup

receivers can fail

Signal DB overflowed

The stored signals database has been overwritten

11/17/06 16:33:23
00001234 E110 01 001

VisorALARM PLUS 2U Operating

III - 18

Doc.DM375-I