Power Connections
The red wire provides power for all Aqua TROLL communication

modes. Analog output is disabled by default. However, the 4-20

mA current loop output can be continuous in Modbus or SDI-12

mode as long as Modbus device register 49507 is set to 1. This

can be done with a connection in Win-Situ by selecting the

Device Setup tab, Analog Setup button, and enabling analog

output.

Communications
The device automatically switches between Modbus and

SDI-12 modes depending on which of the two interfaces has

activity. Modbus and SDI-12 cannot be used at the same time —

whichever one is currently in use will block communication on

the other.
Using Win-Situ Software
Win-Situ provides options for configuring analog/SDI-12

communications (Setup tab) and Modbus communications

(File menu > Settings). In addition, the Aqua TROLL Instrument

is capable of internal logging (programmed in Win-Situ) while

participating in a Modbus, SDI-12, or analog network. However,

Win-Situ cannot communicate with the Aqua TROLL Instrument

while it is trans mitting Modbus, SDI-12, or analog data, and

conversely, the instrument cannot receive or respond to Modbus,

SDI-12, or analog commands while connected to a PC serial port.
Redundant Logging Feature
• If the PLC or recorder somehow loses data, the Aqua TROLL

data can be retrieved using Win-Situ.