Operation – KROHNE BM 26 BASIC_ADVANCED EN User Manual

Page 36

Advertising
background image

6

OPERATION

36

BM 26 BASIC/ADVANCED

www.krohne.com

10/2012 - 4000347004 - HB BM26 Basic/Adv R04 en

Menu overview

Example procedure: Change the indicator units from mm to %

• Push [F

F

F

F] for 3 seconds (button on the back of the indicator board) to access Program mode

Program mode

Program mode

Program mode.

i

In program mode dP

dP

dP

dP is displayed.

• Push [







] 1 time to get to the zero point (ZErO

ZErO

ZErO

ZErO) function.

• Push [F

F

F

F] to access the span range parameter. Make sure that the value is 0.0. Push [







] + [







]

(Escape) to go back to the menu.

• Push [







] 1 time to get to the span range (SPAn

SPAn

SPAn

SPAn) function.

• Push [F

F

F

F] to access the span range parameter.

i

The current value is 600 (example value).

• Push [







] to decrease the value to 100.

• Push [F

F

F

F] to confirm the parameter and go back to the menu.

• Push [







] + [







] (Escape) to go back to the indication.

i

The indication will display a value between 0 and 100 based on a current output of 4...20 mA.

• Put a new sticker (%) on the front of the indicator board.

Function

Function description

Range/Selection list

Default

Decimal Point (dP)

Push [







] or [







] to select

the decimal point position.

Push [F

F

F

F] to confirm.

0…3

1

Zero point (ZErO)

Push [







] or [







] to select

the minimum value. Push

[F

F

F

F] to confirm.

-1999…+9999

0.0

Span range (SPAn)

Push [







] or [







] to select

the maximum value. Push

[F

F

F

F] to confirm.

-1999…+9999

100.0

Input current limit (Li)

Do not use.

n/a

0

Filter (FiLt)

Do not use.

n/a

2

Resolution (riS)

Do not use.

n/a

1