Connect the Earth cord to the Earth (ground) terminal.
It is recommended to connect the positive(+) pole to the earth

side when measuring insulation resistance against the ground or
when a part of the equipment under test is earthed.

With this connection, smaller measured value can be obtained

comparing with other way round.

(1) Check the appropriate voltages to be applied to the circuit

under test, and set the Range switch to any desired insulation
resistance range.

(2) Connect the Earth cord (black) to the Earth terminal of the circuit

under test.

(3) Put the tip of the Line probe (red) to the circuit under test.
Then press the Test button. The buzzer sounds intermittently

during measurement when a range other than 500V is selected.

(4) The measured value will be displayed on the LCD, and it

remains displayed on the LCD after a measurement.

# CAUTION

Turn off the breaker of
the circuit under test.

(5) This instrument has Auto-discharge function.
Keep the test leads connected to the circuit under test and

release the Test button when measurements end. The auto-
discharge function operates to discharge the electrical charges on
the circuit under test. Confirm that the voltage monitor shows 0V.

# DANGER

● Do not touch the circuit under test immediately after testing.
Capacitance stored in the circuit may cause electric shock.

● Leave test leads connected to the circuit and never touch the

circuit until the discharge completes.