KYORITSU 4105A User Manual

Page 10

Advertising
background image

---- 17 ----

9. Before Sending for Service

If this instrument should fail to operate correctly, return it to your nearest

distributor stating the exact nature of the fault. Before returning the

instrument follow the trouble-shooting guide shown below.

If the instrument does not turn on;

Check whether batteries are missing or they are installed incorrect

polarity. Note that batteries were not installed in the instrument at the time

of shipment.

If the display reads ' 1 . . . ' in earth voltage measurement;

A voltage exceeding 200V is being applied to the instrument.

Halt the measurement immediately, otherwise the instrument may be

damaged.

If the display reads ' . . . ' in normal earth resistance measurement;

Stick the auxiliary earth spikes deeper into the earth, or stick them at other

locations; or

Add moisture to the part of the earth where C auxiliary earth spike is stuck

( connected with the red wire ); and

Short the three test leads and check if the display indicates a value near

' 0.00 '. (See section 6 for details.)

If the display reads ' . . . ' in simplified earth resistance measurement;

Check if the connection to a metal water pipe, a common earth of

commercial power supply, etc., is secure; or

Use another metal water pipe, common earth of commercial power

supply, etc.

---- 16 ----

10. Service

If this instrument should fail to operate correctly, return to your nearest

distributors stating the exact nature of the fault.