KYORITSU 4105A User Manual

Page 7

Advertising
background image

---- 10 ----

20

when the earth resistance is low. This indicated value is the earth

resistance of the earthed equipment under test.

Note :

If the auxiliary earth resistance of auxiliary earth spike C is too

high to make measurement, the display reads ' . . . '. Recheck the

connection of test leads and the earth resistance of auxiliary earth

spike.

CAUTION

If measurement is made with the probes twisted or in touch with each

other, the reading of the instrument may be affected by induction. When

connecting the probes, make sure that they are separated.

If earth resistance of auxiliary earth spikes is too large, it may result in

inaccurate measurement. Make sure to stick the auxiliary earth spike P

and C into the moist part of the earth carefully, and ensure sufficient

connections between the respective connections.

6-3 Simplified Measurement (with Test Probe M-7127)

Use this method when the auxiliary earth spike cannot be stuck. In this

method, an existing earth electrode with a low earth resistance, such as

a metal water pipe, a common earth of a commercial power supply and

an earth terminal of a building, can be used with two-terminal method

(E,P).

Use the simplified measurement probe attached which has a convenient

structure that both the safety alligator clip and the test bar are available.

q

Wiring

Make connection as shown in the figure.

---- 11 ----

6-2 Precise Measurement (with Test Probe M-7095)

q

Test probe connection

Stick the auxiliary earth spikes P and C into the ground deeply. They

should be aligned at an interval of 5-10m from the earthed equipment

under test. Connect the green wire to the earthed equipment under

test, the yellow wire to the auxiliary earth spike P and the red wire to

the auxiliary earth spike C from terminals E, P and C of the instrument

in order.

Note :

Make sure to stick the auxiliary earth spikes in the moist part of the

soil. Give enough water where the spikes have to be stuck into the

dry, stony or sandy part of the earth so that it may become moist.

In case of concrete, lay the auxiliary earth spike down and water it,

or put a wet dustcloth etc. on the spike when making measurement.

w

Earth Voltage Measurement

Set the range switch to EARTH VOLTAGE position in the condition of

q

. Earth voltage will be indicated on the display. Make sure that the

voltage is 10V or less.

When the display reads more than 10V, it may result in excessive

errors in earth resistance measurement. To avoid this, make

measurement after reducing the voltage by turning off the power

supply of the equipment under test etc.

e

Precise Measurement

Set the range switch to 2000

position and press the test button. LED

remains illuminated during testing. Turn the range switch to 200

and