Forthisexamplethemaxpermissiblevalueis1667Ω(RCD=30mA

andcontactvoltagelimitof50V).Theinstrumentsreads12.74Ω,

thus the condition RA ≤ 50/Ia is respected. However, considering

thattheRCDisessentialforprotection,itmustbetested(Please

refertoRCDTESTSsection).
TN System
For TN systems the earth fault loop impedance is the sum of the
following impedances.

●Impedanceofthepowertransformersecondarywinding.

●Impedanceofthephaseconductorfromthepowertransformerto

the location of the fault.

●Impedanceoftheprotectiveconductorfromthefaultlocationto

the power transformer.

The figure below shows (dotted line) the Fault loop impedance for
TN systems.

Fig.7-3

According to the International Standard IEC 60364, for TN
system the characteristics of the protective device and the circuit
impedance shall fulfill the following requirement:

Zs x Ia ≤ Uo Where:

Zs is the Fault loop impedance in ohm.
Uo is the nominal voltage between phase to earth (typically 230V

ACforbothsinglephaseandthreephasecircuits).
Ia is the current causing the automatic disconnection of the
protective device within The maximum disconnecting times required

byIEC60364-41thatare: