KYORITSU 4300 User Manual

Page 19

Advertising
background image

̶ 17 ̶

● The displayed value should be less than 10V.

The warning LED starts blinking yellow when the earth voltage

is 10V or higher. (The LED starts blinking at 3V or higher if the

frequency of the earth voltage is 400Hz.)

Ensue that the systems connected to the earth electrode under

test are turned off to get the earth voltages lower when the

warning LED for earth voltage starts blinking. Otherwise, accurate

measured results can not be obtained. The warning LED for earth

voltage may not light up if the frequency is over 400Hz.

● The warning LED starts blinking red with audible warning when

the voltage of 30V or higher is detected. Earth resistance

measurements can not be carried out by pressing the Test

button while the live circuit warning is activating.

(4) Measurement

Press the Test button. The LCD shows the measured result.

The instrument carries out an earth resistance measurement

while the Test button is held down. The buzzer sounds when the

measured value is less than 100Ω.

The measurement is halted when the Test button is released,

and the measured data freezes on the LCD. (The “ ” symbol

appears on the LCD.) A short press of the Test button while the

result is being displayed on the LCD gets the instrument entered

into the Voltage measurement mode.

● The LCD shows “>2099Ω” when the measured result exceeds

the display range. (Over range)

● The instrument automatically enters into the voltage

measurement mode when sensing the live circuit during a

resistance measurement and activates the warning function.

● If an earth resistance measurement is continued at low battery

level with Battery symbol on the LCD, the instrument may be

powered off suddenly.

LED starts blinking.

10V or higher: yellow

30V or higher: red

Fig. 8-5

Advertising