― 8 ―

is updated approximately five times per second.

Overload protection

The continuity test circuit is protected by a 0.5 A
600 V fast acting(HRC)ceramic fuse mounted in
the battery compartment, where a spare fuse is
also stored.
The insulation resistance test circuit is protected by
a resistor against 600 V AC for 10 seconds.

Mains Voltage Indication

On connecting test leads to the circuit under test
on Loop and RCD ranges, the LCD reads V-PE.
Sign "V-PE Lo" or "V-PE Hi" is also shown when
the voltage is 100V or less, or 260V or greater
respectively.

Equipment protected throughout by DOUBLE
INSULATION or REINFORCED INSULATION.
Caution, risk of electric shock.