KYORITSU 6010A User Manual

Page 16

Advertising
background image

― 14 ―

¡ Electronic fluorescent starter switches
¡ Passive infra-red detectors (PIRs)
¡ Dimmer switches
¡ Touch switches
¡ Delay timers
¡ Power controllers
¡ Emergency lighting units
¡ Electronic RCDs
¡ Computers and printers
¡ Electronic point-of-sale terminals (cash registers)
¡ Any other device which includes electronic components.

5

3 Preparation for measurement

Before testing, always check the following:-
1.The“low battery”Indication“

”is not displayed

2.There is no visually obvious damage to the tester or to the test leads
3.Test the continuity of the test leads by switching to continuity test and

shorting out the lead ends. A high reading will indicate that there is a faulty
lead or that the fuse is blown.

4.

MAKE SURE THAT THE CIRCUIT TO BE TESTED IS NOT LIVE.

A

warning lamp is lit if the instrument is connected to a live circuit but test

the circuit as well!

5

4 Insulation resistance measurement

Model 6010A has a single test voltage of 500V DC.
1.Press the test button once. Then, the instrument switches on.
2.Select the insulation resistance setting by rotating the function dial to

“insulation”test section of the functional switch, after making sure that the

instrument is not connected to a live circuit.

3.Attach the test leads to the instrument and to the circuit or the appliance

under test (see Figs 7 & 8)