DENSITY CORRECTION FACTORS

SCFM (indicated) x (CF) = SCFM (Actual) CF = (f1) x (f2) X (f3)
Note: all correction factors need not be used.

Table 1. (f1) PRESSURE CORRECTION FACTORS (inlet pressure)

Table 2. (f2) TEMPERATURE CORRECTION FACTORS

Table 3. (f3) SPECIFIC GRAVITY CORRECTION FACTOR

f1= correction factor for other than 100 PSI inlet.

f2= correction factor for other than 70ºF.

f3= correction factor for other than air at 1.0 Sp. Gr.

Correction Factors
If a Lake meter is installed in a system where conditions differ from
the standard listed above, correction factors will need to be applied to
retain the design accuracy of the meter. The appropriate correction
factor equations are detailed above. To assure the best monitoring
accuracy, pressure and temperature measurements should be taken
directly at the meter’s inlet port.

Special Scales
Special calibrations can be performed by Lake Monitors to correct for
the following system characteristics:

system pressure

system temperature

media specific gravity

various measuring units (i.e. LPM, LPS, m3/hr, etc.)

any combination of the above

Consult Lake’s factory or your distributor for details and prices.

Page 12 / Flow Meters / Lake Manual

f1 =

14.7 + psig

114.7

f2 =

530

460 + ºF

f3 =

1

Sp. Gr.

psig

25

50

75

100 125 150 175 200

f1

.56

.75

.88

1.0 1.11 1.2 1.29 1.37

ºF

10º

30º

50º

70º 90º 110º 130º 150º

f2 1.08 1.04 1.02 1.0 .98 .96 .95 .93