Rola-Chem RC554P pH Digital Controller User Manual

Page 11

Advertising
background image

Rola-Chem Digital Controller

PN 554236 02/17/2014

Page: 11 of 12

6.3 Set-points not being reached or maintained

*

Factory setting for feed time is 0.6 sec on with 5 minute delay. Feeders may require

longer feed time. If time is too short, set-points will not be maintained. If time is too long,
overfeeding chemicals will occur. Correct time is dependent of multiple factors such as
pool/spa water volume, feeder output, chemical concentration and chemical needs.

* Controllers are designed to maintain set-points. Do not expect Controllers to make

major adjustments—major changes should be done manually.

* Pump/feeders must be large enough to reach desired set-points in a relatively short

time. Automation using controllers may require larger feeder or more concentrated
chemicals than system that uses continuous time controlled feeding (i.e. feeders only).

7.0 Warranty and Service-

Limited Warranty
Rola-Chem Corporation warrants the original purchaser that this unit is free from
manufacturing defects in material and workmanship from the date of the original purchase
for one (1) year. If this unit fails within the one (1) year period, it will be repaired or
replaced (Rola-Chem’s option) at no charge, when returned to Rola-Chem Corporation
with proof of purchase receipt. This warranty does not apply to any product damage
caused by improper use, accident, misuse, improper line voltage, fire, flood, lightening,
earthquake or other acts of nature, or, if product was altered or opened by anyone other
than qualified Rola-Chem personnel.

All expendable items- hoses, etc., are not covered under this warranty.
Heavy duty probes are warranted from the date of original purchase for one (1) year.

Rola-Chem Corporation, under no circumstances, shall be liable for any consequential
damages directly or indirectly caused by this unit. Please observe all rules and regulations
required by state and local regulations, building codes, health codes, OSHA, etc.

Service Procedure : For operation assistance in the United State, please call:

(800) 549-4473 or FAX (651)-653-0989

Monday thru Friday 8:00 am-5:00 pm, Central Time.

Rola-Chem Corporation has specialized knowledge and equipment to properly test your
unit and help you with special problems. After talking to our service personnel, the product
in need of service should be shipped with RGA#, freight prepaid, via UPS if possible to: