Configuration level

Configuration parameters

38

KS 90-1 / KS 92-1

Name

Value range

Description

Default

HC.AL

Heating current alarm signal (only visible when O.TYP=0)

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal (only visible when

O.TYP=0)

0

0

not active

1

active

FAi.1
FAi.2
FAi.3

INP1/ INP2 / INP3 error (only visible when O.TYP=0)

1

0

not active

1

active

dP.Er

PROFIBUS error

0

0

not active

1

active: Profibus trouble, no communication with this

instrument.

fOut

Forcing OUT3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Out.5

/

Out.6

Configuration parameters Out.2 = Out.1 except for: Default

Y.1 = 0 Y.2 = 0

g

Method of operation and usage of output

Out.1 to Out.6:

Is more than one signal chosen active as source, those signals are OR-linked.

LOGI

Name

Value range Description

Default

L_r

Local / Remote switching (Remote: adjusting of all values by

front keys is blocked)

0

0

no function (switch-over via interface is possible)

1

always active

2

DI1 switches

3

DI2 switches (basic instrument or OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches

SP.2

Switching to second setpoint

SP.2

0

0

no function (switch-over via interface is possible)

2

DI1 switches

3

DI2 switches (only visible with OPTION)

4

DI3 switches (only visible with OPTION)

5

è - key switches