background image

4.4 Switching behaviuor

With these controllers, configuration parameter

CYCL (ConF/ Cntr/ CYCL)

can be used for matching the cycle time of 2-point and 3-point controllers. This
can be done using the following 4 methods.

4.4.1 Standard (

CyCl= 0 )

The adjusted cycle times

t1 and t2 are valid for 50% or -50% correcting varia-

ble. With very small or very high values, the effective cycle time is extended to
prevent unreasonably short on and off pulses. The shortest pulses result from ¼
x

t1 or ¼ x t2. The characteristic curve is also called “bath tub curve”

Parameters to be adjusted:

t1 : min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

4.4.2 Switching attitude linear (

CyCl= 1 )

For heating (

Y1), the standard method (see chapter 4.4.1) is used. For cooling

(

Y2), a special algorithm for cooling with water is used. Generally, cooling is en-

abled only at an adjustable process temperature (

E.H2O), because low temperatu-

res prevent evaporation with related cooling, whereby damage to the plant is
avoided. The cooling pulse length is adjustable using parameter

t.on and is fi-

xed for all output values.
The “off” time is varied dependent of output value. Parameter

t.off is used for

determining the min “off” time. For output of a shorter off pulse, this pulse is
suppressed, i.e. the max. effective cooling output value is calculated according to
formula

t.on / ( t.on + t.off) w 100%.

Parameters to be adjusted:

E.H2O: minimum temperature for water cooling

(

PArA / Cntr)

t.on:

pulse duration water cooling

t.off: minimum pause water cooling

Configuration level

KS 90-1 / KS 92-1

45

Switching behaviuor

0,0

1,0

2,0

3,0

4,0

5,0

6,0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

Controller output [%]

re

lat

ive

cycle

duration

T / T

1

t1

2 x

t1

3 x

t1

4 x

t1