Constant period 47, Configuration level – West Control Solutions KS 92-1 User Manual

Page 47

Advertising
background image

4.4.4 Heating and cooling with constant period (

CyCl= 3 )

1 and

t2 are met in the overall output

range . To prevent unreasonably short
pulses, parameter

tp is used for adju-

sting the shortest pulse duration. With
small correcting values which require a
pulse shorter than the value adjusted in
tp, this pulse is suppressed. However,
the controller stores the pulse and totali-
zes further pulses, until a pulse of dura-
tion

tp can be output.

Parameters to be adjusted:

t1 : Min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 : min. cycle time 2 (cooling) [s]

tp:

min. pulse length [s]

Configuration level

KS 90-1 / KS 92-1

47

Switching behaviuor

50%

50%

t1 t2

/

tp

tp

30%

70%

20%

80%

10%

90%

t1 t2

/