TABLE 3-1 PROGRAM MODE CONFIGURATION PROCEDURE

Press the SCROLL key until Prog is displayed. Press the DOWN key to enter the Program
mode. Pen 1 will be displayed in the upper display. To enter the Pen 1 parameter, press the
DOWN key. To enter the Pen 2 parameter, if provided, press the SCROLL key, then the
DOWN key. To enter the unit parameter, press the SCROLL key with either Pen 1 or Pen 2
displayed until unit is displayed, then press the DOWN key. Press the SCROLL key to
advance the display through the parameter codes and their values. Use the UP and DOWN
keys to adjust the values. After adjusting a parameter, press the SCROLL key to proceed to
the next parameter. After all selections have been made, press the UP key with a parameter
in the display (not a setting) to exit the mode. For two pen instruments the parameters and
values which are applicable to Pen 1 will appear in the upper display, then the parameters
and values which are applicable to Pen 2 will appear in the lower display. Then the unit
parameters and values will appear in the upper display.

For illustration purposes all available Program mode parameters have been listed. The
parameters that will appear on the specific instrument will depend upon the model number
(hardware configuration) of the instrument and on the parameter selections previously made.

For future reference, record the parameter selections for the application in the “Your Setting”
column and on the Software Reference Sheet in Appendix E (Page 72). Use the Software
Reference Sheet to program the instrument.

To prevent unauthorized changes to the Program mode, the mode can be disabled (turned
off) in the Enable mode.

1

Input Select

inPS

0=J T/C degrees C

1

1=J T/C degrees F
2=K T/C degrees C
3=K T/C degrees F
4=T T/C degrees C
5=T T/C degrees F
6=R T/C degrees C
7=R T/C degrees F
8=S T/C degrees C
9=S T/C degrees F
10=E T/ C degrees C
11=E T/C degrees F
12=B T/ C degrees C
13=B T/C degrees F
14=N T/ C degrees C
15=N T/C degrees F
16=C T/ C degrees C
17=C T/C degrees F
20=RTD degrees C
21=RTD degrees F
30=0 to 5 VDC
31=1 to 5 VDC
32=0 to 50 mVDC
33=10 to 50 mVDC
34=0 to 25 mVDC

2

Input Correction

iCor

-300 to 300 degrees/units

0

3

Output 1

out1

0 = None

0

1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning -Reverse
5=Current Proportioning -Direct
6=Current Proportioning -Reverse
7=Position Proportioning (open)

NOTE:
Fault Detection is not functional
for 0-5V or 0-20mA inputs.

DISPLAY AVAILABLE

FACTORY YOUR

STEP

DESCRIPTION

CODES SETTINGS

SETTING SETTING