West Control Solutions MRC 7000 Controller Manual User Manual
Page 35
Advertising
35
11
Automatic Reset
ArSt
0.0 to 100.0 repeats
0.0
Integration
per minute
(Will be seen if Pb1 or
Pb2 was shown)
12
Rate Derivative
rAtE
0.0 to 10.0 minutes
0.0
(Wll be seen if
Pb1 or Pb2 was seen)
13
Cycle Time Output 1
Ct1
1 to 240 seconds
30
(Will be seen if out1=3,4,7)
14
Cycle Time Output 2
Ct2
1 to 240 seconds
30
(Will be seen if out2=3,4)
15
Position Proportioning
SEnS
0.0 to 50.0 percent
1.0
Sensitivity (Will be seen
if out1=7 and/or out2=0,7)
16
First Output Position
FoP
-1000 to 1000 units
0
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING