External Switch/Relay Contacts

Maximum Contact Resistance (Closure):

50

Minimum Contact Resistance (Open):

5000

External TTL-Compatible Logic Signal

Maximum Voltage (TTL) for “0”:

0.8V

Minimum Voltage (TTL) for “0":

-0.6V

Minimum Voltage (TTL) for “1":

2.0V

Maximum Voltage (TTL) for “1":

24.0V

A.4

TRANSISTOR OUTPUTS

Type:

NPN open collector. Output tied to Alarm 1,

Output 2 tied to Alarm 2.

A.5

RELAY 1 OUTPUT

Contact Type:

Single pole double throw.

Rating:

5A resistive @ 120/240V AC

Lifetime:

>500,000 operations at rated

voltage/current.

Isolation:

Inherent

A.6

RELAY 2 OUTPUT (OPTION)

Contact Type:

Single pole double throw.

Rating:

5A resistive @ 120/240V AC

Lifetime:

>500,000 operations at rated

voltage/current.

Isolation:

Inherent

A.7

LINEAR (RE-TRANSMITTED PV) OUTPUT (OPTION)

Ranges available:

0 - 5V, 1 - 5V, 0 - 10V, 2 - 10V, 0 - 20mA

and 4 - 20mA.

PM091-A

Volume II

A-2

59136