The linearization table is used for input 1

6.3

Input scaling

Scaling of input values is possible. After any linearization, measurement value correction is according to the offset or
two-point method.

g

When using current or voltage signals as input variables for

InP.x, the input and display values

shouldbe scaled at the parameter level. Specification of the input value of the lower and upper scaling
point is in units of the relevant physical quantity.

g

Parameters

InL, OuL, InH and OuH are visible only with ConF / InP / Corr = 3 selected.

Parameters

InL and InH determine the input range.

Example with mA:

InL= 4 and InH = 20 means that measuring from 4 to 20 mA is required (life zero setting).

Functions

TB 45

Input scaling

23

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x

Example for mA/V

Ou.16

Ou.1

.

.

.

.

.

.

In.1

In.16