Table 2: voltage rating and service type – Advanced Protection XGA User Manual

Page 6

Advertising
background image

6

TYPICAL PANEL INSTALLATION

Figure 5

SPD DIMENSIONS: NEMA TYPE 3R

Figure 6

SPD DIMENSIONS: NEMA TYPE 4X PLASTIC

Figure 4

SPD DIMENSIONS: NEMA TYPE 1, 4, AND 4X STAINLESS STEEL

b) The grounding conductor mentioned in item “a” is to

be grounded to earth at the service equipment or other

acceptable building earth ground such as the building

frame in the case of a high-rise steel-frame structure.

c) Any attachment-plug receptacles in the vicinity of the

filter are to be of a grounding type, and the grounding

conductors serving these receptacles are to be connected

to earth ground at the service equipment or other

acceptable building earth ground such as the building

frame in the case of a high-rise steel-frame structure.

d) Pressure terminal or pressure splicing connectors

and soldering lugs used in the installation of the filter

shall be identified as being suitable for the material of

the conductors. Conductors of dissimilar metals shall not

be intermixed in a terminal or splicing connector where

physical contact occurs between dissimilar conductors

unless the device is identified for the purpose and

conditions of use.

Table 2: VOLTAGE RATING AND

SERVICE TYPE

TE & XTE / 1XGA

120/240 Single Phase, 3 Wire, "Grounded"

TE & XTE / 11XGA

120 Single Phase, 2 Wire, "Grounded"

TE & XTE / 12XGA

240 Single Phase, 2 Wire, "Grounded"

TE & XTE / 2XGA

120/208 Three Phase, 4 Wire, "Grounded", WYE

TE & XTE / 3XGA

120/240 Three Phase, 4 Wire, "High-Leg", DELTA

TE & XTE / 4XGA

277/480 Three Phase, 4 Wire, "Grounded", WYE

TE & XTE / 5XGA

480 Three Phase, 3 Wire, DELTA

TE & XTE / 51XGA

480 Three Phase, "Corner Grounded", DELTA

TE & XTE / 6XGA

240 Three Phase, 3 Wire, DELTA

TE & XTE / 61XGA

240 Three Phase, "Corner Grounded", DELTA

TE & XTE / 7XGA

220/380 Three Phase, 4 Wire, "Grounded", WYE

TE & XTE / 8XGA

347/600 Three Phase, 4 Wire, "Grounded", WYE

TE & XTE / 9XGA

600 Three Phase, 3 Wire, DELTA

TE & XTE / 91XGA

600 Three Phase, "Corner Grounded" DELTA