Control and Diagnostic Panel

All indicators and controls are located on the front diagnostic

panel. Green LEDs indicate correct operation.

Phase A, B & C: Tri-Color LED status indicators – one per phase

Green – Full Protection

Amber – Partial Protection

Red – No Protection

Service LED (red): LED illuminates in the event of problem.

This indicator is logic-connected to the Phase LEDs. Should a

Phase LED go out, the red Service LED will illuminate and the

Audible Alarm will sound.

Test: Tests red Service LED and Audible Alarm regardless

of Alarm Silence status; does not cycle optional dry contacts

Alarm Silence: Turns Audible Alarm off (Audible Alarm is

deactivated when LED is illuminated)

Surge Counter Count: (if equipped) Increments optional surge

counter by one (+1)

Surge Counter Reset: (if equipped) Resets optional surge

counter to zero (0)

If an inoperative condition where to occur, the built-in audible

alarm will sound and the red Service LED will illuminate. This

indicates that the unit needs evaluation by a qualified electrician

or technician. Until a qualified person evaluates the unit, press

Alarm Silence to silence the alarm. (The LED above Alarm

Silence illuminates when the alarm is deactivated. Normal

operation occurs with the Alarm Silence LED extinguished.)

The red Service LED will remain illuminated even though the

Audible Alarm has been silenced. Test tests the red.

Service LED and the Audible Alarm

Diagnostics will indicate a failure upon loss of voltage or

significant drop in voltage. Be aware that ground faults

on ungrounded or resistive ground systems will trigger a

failure alarm on this SPD.

If LEDs are illuminated in a manner that suggests

contradictory information, there may be an internal logic

problem and the unit needs replaced. If none of the LEDs

are illuminated, the unit may not be installed correctly. For

troubleshooting assistance, please contact APT Technical

Support at (800) 237-4567.

Surge Counter Options

The surge counter registers the number of transient

overvoltages on all L-N and L-G modes since the counter

was last reset. The counter is inductively coupled from each

mode of protection. It increments upon significant current

change in a short time period (large di/dt).

The surge counter includes Test and Reset buttons on

the touchpad display. Pressing Test adds one count.

Pressing Reset clears the counter’s memory and sets the

display to zero.

The counter option includes a SuperCap internal storage

capacitor that provides backup power for up to four

days in the event of a power outage. This eliminates the

maintenance of battery backups. There is a 10-15 minute

charging cycle before the counter(s) operate.

Single Counter – Totals the surges through the L-N and L-G

Dual Counters – Is used to distinguish between L-N and

L-G surges. Two separate counters are used, with common

Reset and Test tabs.

Supplemental LED indicators on Modules

Each module includes three LEDs per Figure 15. The

center green LED indicates power is on. This green LED

should be illuminated during normal operation.

When the upper left red LED is illuminated, the module’s

L-G protection is lost.

When the upper right red LED is illuminated, the module’s

L-N protection is lost.

MODULE LEDs

Green

LED lit:

power on

Red

LED lit:

loss of surge

suppression

from line to

neutral

Red

LED lit:

loss of surge

suppression

from line to

ground