Table 4: fuse-all series order # part description – Advanced Protection HPS User Manual

Page 10

Advertising
background image

10

MAINTENANCE

SPDs require minimal maintenance. We recommend periodic

inspection of diagnostic indicators to ensure proper operation.

We also recommend keeping the SPD clean as appropriate.

Fuse Replacement

Fuses must be replaced with exact fuse included. These

are special fuses and not typical fuses. Note that fuses

are generally opened by failed modules. Modules can be

removed and checked for short circuit with ohm-meter. Any

reading other than open circuit suggests a failed module. Any

reading <200 Ω positively confirms a failed module. Contact

APT Technical Support as appropriate.

Module Removal & Replacement Instructions

Disconnect power to the SPD. Using an allen wrench, remove

the bolts on both ends of the module, and pull the module

out. Make careful note of the location and part number of

each module removed, as this part number is not referenced

anywhere else on the SPD.

The module(s) should only be replaced with a new module

bearing the same part number as the module(s) being

removed. Replace with a new module by reversing the

procedure. Torque bolts to 65 inch lbs., power up the SPD and

verify the green module LED is lit and all alarms have cleared.

Display Replacement

The display is field replaceable. Service should only

be performed by qualified persons. Deenergize SPD,

confirm with appropriate measurement equipment and

discharge internal capacitance to ground. Mark locations

and carefully disconnect diagnostic cables, contacts,

connecting conductors, etc. Unbolt display and replace.

Reinstall in reverse.

Note that a sealing gasket between the display and the

enclosure is a key component ensuring weather resistance.

Replace the gasket whenever the display is removed.

Diagnostic Board Removal & Replacement Instructions

Disconnect power to the SPD. Remove the board

from the standoffs. Remove the connectors one at a

time from the existing board and insert them into the

appropriate connector on the replacement board. Install

the replacement board onto the standoffs.

Troubleshooting & Service

Please contact us for any service related issues. We want

to take care of any problems.

Quality SPDs are designed and tested to withstand severe

duty. However, there are various electrical anomalies that

SPDs cannot protect against. These are generally Sustained

Overvoltages also known as Temporary Overvoltages

(TOVs). In this context, Sustained Overvoltages may be only

a few cycles. Failed SPDs tend to be symptoms, not root

causes. A failed SPD should be treated as a ‘canary in the

coalmine’ suggesting further investigation as there may be

a larger issue at play. Regardless of cause, SPDs attempt

to protect their load until failure.

As noted above, the single largest ‘killer’ of SPDs is

reference to ground issues. If the SPD shows problems on

startup, there is reasonable chance of bonding/grounding/

misapplication issue. This permanently damages the unit.

If not corrected, it will happen again.

Table 3:

MODULE REMOVAL & REPLACEMENT

Order #

Part Description

MA120

120VAC Module with Indicator LED

MA120CX

120VAC Module with Indicator LED

MA120CL

120VAC Module with Indicator LED

MA120NI

120VAC Module with NO Indicator LED

MA120NICX

120VAC Module with NO Indicator LED

MA120NICL

120VAC Module with NO Indicator LED

MA240

240VAC Module with Indicator LED

MA240CX

240VAC Module with Indicator LED

MA240CL

240VAC Module with Indicator LED

MA240NI

240VAC Module with NO Indicator LED

MA240NICX

240VAC Module with NO Indicator LED

MA240NICL

240VAC Module with NO Indicator LED

MA277

277VAC Module with Indicator LED

MA277CX

277VAC Module with Indicator LED

MA277CL

277VAC Module with Indicator LED

MA277NI

277VAC Module with NO Indicator LED

MA277NICX

277VAC Module with NO Indicator LED

MA277NICL

277VAC Module with NO Indicator LED

MA347

347VAC Module with Indicator LED

MA347CX

347VAC Module with Indicator LED

MA347CL

347VAC Module with Indicator LED

MA347NI

347VAC Module with NO Indicator LED

MA347NICX

347VAC Module with NO Indicator LED

MA347NICL

347VAC Module with NO Indicator LED

Table 4: FUSE-ALL SERIES

Order #

Part Description

7294

APT 100-2 Fuse

Tip: Visually confirm N-G bonding. Be aware that a voltmeter

measuring N-G can be misleading. For example, N-G voltage

could read 0V because neutral and ground are at the same

potential by happenstance, not because they are bonded.

Visually confirm bonding.

Tip: Experience indicates that regulation-challenged generators

can cause Sustained Overvoltages, as well as ungrounded

generators, and/or unusual load transfer systems.

Advertising
This manual is related to the following products:

HP