Advanced Protection HPS User Manual

Page 8

Advertising
background image

NEMA 3R Drain Holes for Standard Steel Enclosure

In order to maintain a UL 3R rating, two 0.25” (6mm) holes

must be drilled in opposite corners of the bottom surface

of the enclosure. Take care to not damage internal SPD

components. Remove any drilling remnants. (Do not perform

on other enclosures or ratings.)

Optional Flush Mount Installation Considerations

The HP and HPS are approximately 6” deep. The unit will not

mount flush unless there is as least 6” of depth clearance.

They are not designed to mount flush on a typical 2 x 4

stud wall.

Back Flange Mounting: Mount as close as possible to

protected panel. Create a wall opening slightly larger than

12”(350mm) x 12”(305mm). See drawing. Configure a robust

backing plate inside the wall cavity 6”(152mm) from the wall

face such that the SPD is supported from its back. Note the

mounting holes on the back flange. Also note that the HP

and HPS weigh 25 lbs. Be careful not to drop the SPD into

the wall. See Figure 4.

Retro-fit Into Existing Panel with No Available

Breaker Positions

These can be difficult with limited options because all

applicable Codes must be followed:

Consider consolidating loads in a manner that might

free breaker positions.

A ten foot tap rule in NEC

®

240.21(B)(1) allows you

to tap the bus as long as the conductors are rated at

least 10% of the ampacity of the panel. This works

well if the panel is about 600A or less: Tap the bus, run

short 6 AWG leads to the SPD. A Disconnect Switch

or Safety Switch allows for easier SPD servicing in

the future. If the panel starts getting large (>800A),

then the conductors may also become too large to fit

into the SPD lugs or too cumbersome to work with.

Consider tapping the bus per NEC

®

240.21(B)(1).

Run appropriate size conductors to a safety switch

fused to 60A. Mount the SPD immediately adjacent

to the safety switch. Connect SPD to the load side

of the safety switch with 6 AWG. Keep all leads as

short as possible.

In no-win situations, consider asking the Authority

Having Jurisdiction (AHJ). Some AHJ’s appreciate

SPD safety benefits on smoke detectors, medical

equipment, security equipment, etc. Similarly, some

AHJ’s appreciate the financial distress of failed

microelectronic loads. Depending on situation, an AHJ

might approve the ‘lesser of two evils’.

OPERATION

Control and Diagnostic Panel

All indicators and controls are located on the front diagnostic

panel. Each phase features a Green LED indicator. Green

LEDs indicate correct operation.

If an inoperative condition were to occur in the HPS, the

green LED(s) will extinguish.

If an inoperative condition were to occur in the HP, the

built-in audible alarm will sound and the red Service LED

will illuminate. This indicates that the unit needs evaluation

by a qualified electrician or technician. Until a qualified

person evaluates the unit, press Alarm Silence to silence

the alarm. (The LED above Alarm Silence illuminates when

the alarm is deactivated. Normal operation occurs with the

Alarm Silence LED extinguished.) The red Service LED

will remain illuminated even though the Audible Alarm has

been silenced. Test tests the red Service LED, the Audible

Alarm, and changes the state of Dry Contacts (if equipped).

If LEDs are illuminated in a manner that suggests

contradictory information, there may be an internal logic

problem and the unit needs replaced. If none of the LEDS

are illuminated, the unit may not be installed correctly. If a

green LED is not illuminated and is suspected of being faulty,

a qualified electrician may attempt to diagnose the problem

by deenergizing the unit, opening the door and swapping

ribbon cable leads. For troubleshooting assistance, please

contact APT Technical Support at (800) 237-4567.

Surge Counter Option

The surge counter registers the number of transient

overvoltages on all L-N and L-G modes since the counter

was last reset. The counter is inductively coupled from each

mode of protection. It increments upon significant current

change in a short time period (large di/dt).

FLUSH MOUNT INSTALLATION

Figure 4

Figure 3

NEMA 3R DRAIN HOLES

Flush Mount front view

Flush Mount Side View

8

Advertising
This manual is related to the following products:

HP