Chillers deltachill, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 23
Chillers
DELTACHILL
™
Chillers
23
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Cooling Performance EC Fans
Ambient (°C)
25
30
35
40
Model
Vorlauftemperatur
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC036DR-06BMS0
5
380.3
107.2
360.2
116.5
338.6
126.7
315.5
138.0
6
392.0
107.9
371.3
117.3
349.1
127.5
325.3
138.8
7
403.8
108.7
382.5
118.1
359.7
128.3
335.3
139.6
8
415.8
109.4
393.9
118.8
370.5
129.1
345.4
140.4
9
427.9
110.2
405.5
119.6
381.4
129.9
355.7
141.2
10
440.2
110.9
417.2
120.4
392.5
130.8
366.1
142.1
DCC038DR-10BMS0
5
394.5
99.0
375.4
108.1
354.9
118.1
332.9
129.0
6
407.0
99.5
387.4
108.7
366.3
118.7
343.7
129.6
7
419.7
100.1
399.6
109.3
378.0
119.3
354.8
130.3
8
432.6
100.6
412.0
109.9
389.8
119.9
366.0
130.9
9
445.8
101.2
424.6
110.4
401.8
120.5
377.4
131.5
10
459.2
101.8
437.5
111.1
414.1
121.1
389.1
132.1
DCC039DR-06BSS0
5
418.7
122.9
396.0
133.5
371.3
145.0
344.7
157.7
6
431.5
123.8
407.9
134.3
382.5
145.9
355.2
158.5
7
444.3
124.6
420.1
135.1
393.9
146.7
365.9
159.4
8
457.2
125.4
432.3
136.0
405.5
147.6
376.7
160.3
9
470.4
126.2
444.8
136.8
417.3
148.4
387.7
161.2
10
483.7
127.0
457.4
137.7
429.2
149.3
398.9
162.1
DCC042DR-10BSS0
5
435.4
112.9
414.4
123.3
391.8
134.7
367.3
147.2
6
449.1
113.5
427.6
123.9
404.4
135.3
379.2
147.8
7
463.1
114.1
441.1
124.5
417.2
136.0
391.4
148.5
8
477.3
114.8
454.7
125.2
430.2
136.6
403.8
149.2
9
491.8
115.4
468.6
125.8
443.5
137.3
416.3
149.9
10
506.5
116.1
482.7
126.5
457.0
138.0
429.2
150.6
DCC043DR-08BST0
5
464.4
129.2
440.8
140.7
415.5
153.4
387.8
167.2
6
478.8
130.1
454.6
141.7
428.6
154.4
399.9
168.1
7
493.5
131.0
468.6
142.6
441.8
155.3
412.3
169.0
8
508.4
131.9
482.9
143.6
455.2
156.2
424.8
169.9
9
523.5
132.8
497.4
144.5
468.8
157.2
437.6
170.9
10
539.0
133.8
512.0
145.5
482.5
158.1
450.6
171.8
DCC045DR-10BST0
5
472.2
124.6
448.8
136.0
423.6
148.4
396.6
162.1
6
487.0
125.4
463.0
136.8
437.1
149.2
409.4
162.9
7
502.1
126.2
477.4
137.6
450.9
150.1
422.4
163.8
8
517.4
127.0
492.1
138.4
464.8
150.9
435.6
164.6
9
533.1
127.8
507.0
139.3
479.0
151.8
449.1
165.5
10
548.9
128.6
522.2
140.1
493.5
152.7
462.7
166.4
DCC046DR-08BTT0
5
495.0
141.3
469.3
153.9
442.0
167.6
411.7
182.4
6
510.2
142.4
483.9
155.0
455.8
168.8
424.3
183.4
7
525.7
143.5
498.6
156.1
469.7
169.9
437.1
184.4
8
541.4
144.6
513.7
157.3
483.6
170.9
450.0
185.5
9
557.4
145.7
528.9
158.4
497.6
172.0
463.2
186.6
10
573.7
146.8
544.4
159.6
511.8
173.1
476.5
187.7
DCC048DR-10BTT0
5
503.8
136.1
478.4
148.5
451.1
161.9
422.1
176.7
6
519.5
137.1
493.3
149.4
465.4
162.9
435.6
177.7
7
535.4
138.0
508.6
150.4
479.9
163.9
449.2
178.8
8
551.7
139.0
524.1
151.4
494.6
164.9
463.1
179.8
9
568.2
140.0
539.8
152.4
509.5
166.0
477.3
180.9
10
584.9
140.9
555.8
153.5
524.8
167.1
491.6
181.9
DCC051DR-08BVV0
5
551.6
160.9
520.3
177.2
487.4
195.5
452.6
216.1
6
567.7
162.0
535.6
178.3
501.8
196.7
466.0
217.3
7
584.1
163.1
551.1
179.5
516.5
197.9
479.7
218.6
8
600.7
164.3
566.9
180.7
531.3
199.1
493.6
219.9
9
617.6
165.4
582.9
181.9
546.4
200.4
507.8
221.2
10
634.7
166.6
599.1
183.1
561.7
201.7
522.1
222.5
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.