Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Mechanical Cooling EC Fans Regular Quiet

Ambient (°C)

25

30

35

40

Model

Supply Temp

Output

Input

Output

Input

Output

Input

Output

Input

°C

kW

kW

kW

kW

kW

kW

kW

kW

DCF013DR-04ACD0

6

135.6

33.1

128.9

36.3

121.7

39.8

114.0

43.8

7

139.8

33.3

132.9

36.5

125.6

40.1

117.7

44.1

8

144.1

33.5

137.1

36.7

129.5

40.3

121.5

44.3

10

153.0

34.0

145.6

37.2

137.7

40.8

129.2

44.8

12

162.2

34.5

154.4

37.7

146.1

41.3

137.2

45.3

14

171.6

35.0

163.4

38.2

154.8

41.8

145.5

45.8

DCF014DR-04ADD0

6

149.7

38.3

142.4

41.9

134.5

45.8

125.9

50.2

7

154.3

38.6

146.9

42.1

138.8

46.1

130.0

50.5

8

159.1

38.8

151.4

42.4

143.1

46.3

134.2

50.7

10

168.9

39.3

160.8

42.9

152.1

46.9

142.7

51.3

12

179.0

39.8

170.5

43.4

161.3

47.4

151.5

51.9

14

189.3

40.4

180.4

44.0

170.9

48.0

160.5

52.4

DCF015DR-04ADF0

6

163.0

42.4

154.8

46.3

146.1

50.6

136.7

55.4

7

168.1

42.7

159.7

46.6

150.7

50.9

141.1

55.7

8

173.2

43.0

164.6

46.9

155.4

51.3

145.6

56.1

10

183.8

43.7

174.7

47.6

165.0

52.0

154.7

56.8

12

194.7

44.3

185.2

48.3

175.0

52.7

164.2

57.5

14

206.0

45.0

196.1

49.0

185.3

53.4

174.0

58.3

DCF016DR-04AJJ0

6

169.4

44.6

160.7

48.8

151.5

53.5

141.9

58.8

7

174.8

44.9

165.9

49.1

156.5

53.8

146.6

59.2

8

180.3

45.2

171.2

49.4

161.6

54.2

151.4

59.5

10

191.6

45.8

182.0

50.1

171.9

54.9

161.3

60.2

12

203.3

46.5

193.2

50.8

182.6

55.6

171.5

61.0

14

215.3

47.2

204.7

51.5

193.6

56.4

182.0

61.7

DCF018DR-04BJK0

6

197.8

54.3

187.4

59.5

176.1

65.1

164.1

71.5

7

203.9

54.7

193.2

59.9

181.6

65.5

169.3

71.9

8

210.2

55.1

199.0

60.3

187.1

66.0

174.5

72.3

10

222.9

56.0

211.0

61.1

198.5

66.8

185.3

73.2

12

235.8

56.8

223.4

62.0

210.3

67.7

196.3

74.1

14

249.1

57.7

236.0

62.9

222.3

68.6

207.7

75.0

DCF020DR-06BFK0

6

206.2

50.9

195.9

55.9

184.9

61.5

173.2

67.7

7

212.6

51.3

202.0

56.3

190.8

61.9

178.8

68.1

8

219.1

51.6

208.3

56.7

196.7

62.2

184.4

68.5

10

232.5

52.4

221.1

57.4

208.9

63.0

196.1

69.3

12

246.2

53.2

234.3

58.2

221.6

63.8

208.1

70.1

14

260.4

54.0

247.9

59.1

234.6

64.7

220.5

70.9

DCF023DR-06BKK0

6

231.9

58.5

220.1

64.5

207.8

71.1

194.7

78.7

7

239.0

58.9

227.0

64.9

214.3

71.6

201.0

79.1

8

246.3

59.4

234.0

65.3

221.0

72.0

207.4

79.5

10

261.2

60.3

248.3

66.2

234.8

72.9

220.5

80.4

12

276.5

61.2

263.2

67.2

249.0

73.9

234.0

81.4

14

292.4

62.2

278.4

68.2

263.6

74.8

248.0

82.4



1

Output kW refers to the chilled water duty.

2

Input kW refers to the unit input power (compressor + fans).

3

Duties applicable for chilled water

T between 4 and 8°C.

4

Interpolate for water temperatures between those quoted, do not extrapolate.

5

Water flow rate (l/s) = Output ÷ (Cp x

T)

6

For conditions outside of those quoted please refer to Airedale.