Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC046DX-10BTT0

DCC048DX-12BTT0

DCC051DX-10BVV0

Unit Data

Nominal Run Amps

(1)

A

309.9

314.9

356.2

Maximum Start Amps

(2)

A

582.5

587.5

568.0

Recommended Mains Fuse Size

A

355

355

400

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

10

12

10

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

10

12

10

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 47.5

47.5 / 47.5

55.2 / 55.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

28.2 / 28.2

28.2 / 28.2

33.1 / 33.1

Sump Heater Rating

W

130

130

140

Start Amps (2)

A

320 / 320

320 / 320

267 / 267

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

42.8

50.3

Circuit 2 Comp RLA (PFC)

42.8

42.8

50.3

Nominal Run Amps

A

281.7

286.7

326.7

Maximum Start Amps

A

558.9

563.9

543.5

Compressor Nominal Run Amps

A

42.8 / 42.8

42.8 / 42.8

50.3 / 50.3

Recommended Mains Fuse Size

A

355

355

400

Electronic Soft-start

Nominal Run Amps

A

309.9

314.9

356.2

Maximum Start Amps

A

454.5

459.5

461.2

Recommended Mains Fuse

A

355

355

400

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

281.7

286.7

326.7

Maximum Start Amps

A

430.9

435.9

436.7

Compressor Nominal Run Amps

A

42.8 / 42.8

42.8 / 42.8

50.3 / 50.3

Recommended Mains Fuse Size

A

355

355

400

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

12

12

Unit Nominal Run Amps

A

321.94

326.94

368.2

Recommended Mains Fuse Size

A

355

355

450

Motor Rating

kW

5.5

5.5

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

14

Unit Nominal Run Amps

A

323.9

328.9

370.2

Recommended Mains Fuse Size

A

355

355

450

Motor Rating

kW

7.5

7.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

321.1

326.1

367.4

Recommended Mains Fuse Size

A

355

355

450

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

324.7

329.7

371.0

Recommended Mains Fuse Size

A

355

355

450

Motor Rating

kW

7.5

7.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.