ELECTRICAL DATA

46

47

48

Unit Data

DCF088TR-19HYYV

DCF090TR-20HYVV

DCF095TR-21HVVV

Nominal Run Amps

(1)

A

555.1

584.3

613.8

Maximum Start Amps

A

783.5

812.7

822.2

Recommended Mains Fuse Size

A

630

630

670

Evaporator
Immersion Heater Rating

W

250

250

250

Condenser Fan - Per Fan (AC)
Quantity

19

20

21

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15.0

15.0

15.0

Motor Rating

kW

2.0

2.0

2.0

Condenser Fan - Per Fan (EC)
Quantity

19

20

21

Full Load Amps

A

3.9

3.9

3.9

Motor Rating

kW

2.6

2.6

2.6

Condenser Fan - Per Fan (EC+)

2.6

2.6

2.6

Quantity

19

20

21

Full Load Amps

A

4.5

4.5

4.5

Motor Rating

kW

2.9

2.9

2.9

Compressor - Per Compressor
Nominal Run Amps

A

47.5 / 47.5 / 55.2

47.5 / 55.2 / 55.2

55.2 / 55.2 / 55.2

Quantity

3 + 3 + 3

3 + 3 + 3

3 + 3 + 3

Motor Rating

kW

29.6 / 29.6 / 33.1

29.6 / 33.1 / 33.1

33.1 / 33.1 / 33.1

Sump Heater Rating

W

140

140

140

Start Amps

(2)

A

287 / 287 / 267

287 / 267 / 267

267 / 267 / 267

OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)

(3)

Nominal Run Amps

A

505.8

526.1

546.5

Reactive power reduction/saving

(4)

kVAr

83.1

95.9

108.6

Maximum Start Amps

A

734.2

754.5

754.9

Recommended Mains Fuse Size

A

630

630

670

Electronic Soft-start
Nominal Run Amps

A

555.1

584.3

613.8

Maximum Start Amps

A

668.7

697.9

715.4

Recommended Mains Fuse

A

630

630

670

Power Factor Correction (PF 0.98)

& Electronic Soft Start

(3)

Nominal Run Amps

A

505.8

526.1

546.5

Maximum Start Amps

A

619.4

639.7

648.1

Recommended Mains Fuse Size

A

630.0

630.0

670.0

Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

28.5

28.5

28.5

Unit Nominal Run Amps

A

583.5

612.8

642.3

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

16.4

16.4

16.4

Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps

A

35.0

35.0

35.0

Unit Nominal Run Amps

A

590.0

619.3

648.8

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

20.3

20.3

20.3

Standard Head Inverter Pump

(Single or Run/Standby)
Pump Full Load Amps

A

26.9

26.9

26.9

Unit Nominal Run Amps

A

576.2

605.2

634.4

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

16.8

16.8

16.8

Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps

A

33.2

33.2

33.2

Unit Nominal Run Amps

A

581.1

610.1

639.3

Recommended Mains Fuse Size

A

630

670

670

Motor Rating

kW

20.7

20.7

20.7

(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.

DCF Electrical Data - Regular Quiet