Page 145: Dcf electrical data - regular quiet
145
Chiller Technical Manual 7267818 V1.4.0_04_2014
Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
Fre
eC
oo
l
ELECTRICAL DATA
46
47
48
Unit Data
DCF088TR-19HYYV
DCF090TR-20HYVV
DCF095TR-21HVVV
Nominal Run Amps
(1)
A
555.1
584.3
613.8
Maximum Start Amps
A
783.5
812.7
822.2
Recommended Mains Fuse Size
A
630
630
670
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (AC)
Quantity
19
20
21
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15.0
15.0
15.0
Motor Rating
kW
2.0
2.0
2.0
Condenser Fan - Per Fan (EC)
Quantity
19
20
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Condenser Fan - Per Fan (EC+)
2.6
2.6
2.6
Quantity
19
20
21
Full Load Amps
A
4.5
4.5
4.5
Motor Rating
kW
2.9
2.9
2.9
Compressor - Per Compressor
Nominal Run Amps
A
47.5 / 47.5 / 55.2
47.5 / 55.2 / 55.2
55.2 / 55.2 / 55.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.6 / 29.6 / 33.1
29.6 / 33.1 / 33.1
33.1 / 33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
287 / 287 / 267
287 / 267 / 267
267 / 267 / 267
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
505.8
526.1
546.5
Reactive power reduction/saving
(4)
kVAr
83.1
95.9
108.6
Maximum Start Amps
A
734.2
754.5
754.9
Recommended Mains Fuse Size
A
630
630
670
Electronic Soft-start
Nominal Run Amps
A
555.1
584.3
613.8
Maximum Start Amps
A
668.7
697.9
715.4
Recommended Mains Fuse
A
630
630
670
Power Factor Correction (PF 0.98)
& Electronic Soft Start
(3)
Nominal Run Amps
A
505.8
526.1
546.5
Maximum Start Amps
A
619.4
639.7
648.1
Recommended Mains Fuse Size
A
630.0
630.0
670.0
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
583.5
612.8
642.3
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
590.0
619.3
648.8
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
576.2
605.2
634.4
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
581.1
610.1
639.3
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet