Where the system permanent heat load is known, the minimum water volume in litres Vmin is:

Vmin = Water Flow Rate (litres/minute) x Minimum Compressor Run Time (mins) x Chiller Loading Factor

Where
Vmin is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes

Minimum System Water Volume Calculations

Example:

Chiller at 35°C Ambient, 7/12°C Water, Model DCF046DR-07DXY0 with a permanent load of 191.2 kW

Unit capacity at design conditions =

478 kW

Permanent Heat Load

=

191.2kW

Minimum Turndown

=

16%

Where the system permanent heat load is unknown:

Vmin

=

Water Flow Rate (litres/hour) x Minimum turndown ratio x 1.2

Maximum number of compressor starts (per hour)

Example:

Chiller at 35°C Ambient, 7/12°C Water, Model DCC046DR-07DXY0

Unit capacity at design conditions =

478 kW

Minimum Turndown

=

16% (0.16)

METHOD 2

METHOD 1

= Vmin =

478 x 60

x 2 x (478 x 0.16) x 1.2 = 1314.2 Litres

4.19 x 5

191.2

Vmin = 478 x 3600 x 0.16 x 1.2

=

1314.2 Litres

4.19 x 5

12

Chiller loading factor =

Minimum Turndown (kW) x 1.2

Permanent Heat Load