Chiller Technical Manual 7267818 V1.4.0_04_2014

In

sta

lla

tio

n

Chillers

DeltaChill™Air Cooled and FreeCool

Installation Data

Unit Lifting

Employ lifting specialists

Local codes and regulations relating to the lifting of this type of equipment should be observed

Use the appropriate spreader bars/lifting slings (provided by others) with the eye bolts/lugs provided.

Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided; each individual chain must be

capable of lifting the whole unit

Lifting Eye size is 40mm.

Lifting Dimensions

C

A1

Dimension (mm)

A1 (Min) A2 (Min)

B

C

7 / 8 Fan Unit

4000

N/A

N/A

3680

9 / 10 Fan Unit

5000

N/A

N/A

4415

11 / 12 Fan Unit

3500

3000

2340

3145

13 / 14 Fan Unit

4500

3000

2340

4077

15 / 16 Fan Unit

5000

3000

2800

4750

17 / 18 Fan Unit

6000

3000

2950

5730

19 / 20 Fan Unit

7000

4000

3150

6660

21 / 22 Fan Unit

7000

5000

4000

6930

IMPORTANT

Do not use 1 chain between 2 lifting points to avoid load shift.

Only use lifting points provided.

Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage.

Lift the unit slowly and evenly.

If the unit is dropped, it should immediately be checked for damage and reported to Airedale.