Ultima compact freecool chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 44: Mechanical data

Advertising
background image

ULTIMA COMPACT FREECOOL

Chillers

44

Chillers

Technical Manual : 6259576 V1.2.0_02__2013

General Specification

MECHANICAL DATA

UCFC300D-8/2

UCFC330D-10/2

UCFC360D-10/2

UCFC400D-12/2

UCFC450D-12/2

Cooling Duty

DX Cooling Output

(1)

kW

305.3

341.4

366.7

412.8

455.9

Nom Input (Compressor only)

(1)

kW

104.0

112

126.1

138.9

155.8

EER - DX (Mechanical)

(2)

2.94

3.05

2.91

2.97

2.93

Free Cooling

(3)

kW

153.0

191.0

193.0

231.0

236.0

Capacity Steps

%

0, 25, 50, 75 & 100

0, 19, 33, 52, 67,

85 & 100

0, 17, 33, 50, 67,

83 & 100

0, 18, 33, 51, 67,

85 & 100

0, 17, 33, 50, 67,

83 & 100

Dimensions

2180 x 2200 x

4720

2180 x 2200 x

5570

2180 x 2200 x

5570

2180 x 2200 x

6420

2180 x 2200 x

6420

H x W x L

mm

Weight

(4)

Machine

kg

2930

3540

3540

3970

4050

Operating

kg

3250

3930

3930

4420

4510

Construction - Material / Colour

Base: Plain Galvanised Steel

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)

Evaporator

Stainless Steel Brazed Plate

Insulation

Class 1

Water Volume

l

28.8

35.1

35.1

39.6

46.8

Total Max. Water Flow

l/s

22.9

25.7

27.4

30.9

34.2

Condenser

Copper Tube/ Aluminium Fins

Face Area (Total)

11.22

14.03

14.03

16.83

16.83

Nominal Airflow

m³/s

19.60

24.50

24.50

29.40

29.40

Fan & Motor

Sickle Bladed Fan

Quantity

8

10

10

12

12

Diameter

mm

710

710

710

710

710

Maximum Speed

rpm

900

900

900

900

900

Compressor

Tandem

Trio

Trio

Trio

Trio

Quantity

2 + 2

3 + 3

3 + 3

3 + 3

3 + 3

Oil Charge Volume (Total)

l

2 x 8.0 + 2 x 8.0

3 x 8.0 + 3 x 8.0

3 x 8.0 + 3 x 8.0

3 x 8.0 + 3 x 8.0

3 x 8.0 + 3 x 8.0

Oil Type

Polyol Ester

Refrigeration

Dual Circuit

Refrigerant Control

Electronic Expansion Valve (EEV)

Refrigerant Precharged

R407C

Charge (Total)

kg

39 + 39

49 + 45

47 + 47

57 + 53

56 + 56

Connections

Water Inlet / Outlet - Unit

PN16 DN100

PN16 DN100

PN16 DN100

PN16 DN100

PN16 DN100

Water Drain/Bleed - Evap

in

1/2

1/2

1/2

1/2

1/2

Water System

Min. System Water Volume

(5)

l

1374

1168

1122

1337

1395

Max. System Operating Press

Bar

10

10

10

10

10

OPTIONAL EXTRAS

Water Pump

(1)

In Line Pump

Single Head or Run/Standby

Nom External Head - Standard

kPa

151

138

121

125

108

Nom External Head - Larger

kPa

218

206

190

196

182

Twin Head

Nom External Head - Standard

kPa

144

129

110

109

87

Nom External Head - Larger

kPa

213

198

180

181

161

(1)

Based on 12/7°C water temperature and 30°C ambient with a 20% Ethylene Glycol Water Concentration as quoted in

Capacity Data

– DX

Mechanical Cooling

, on page 20.

(2)

EER is the DX (Mechanical) Output Duty

Nominal Input.

(3)

Based on flow rate at 12/7°C water temperature and 30°C air on coil, 12°C return water temperature @ 5°C ambient with a 20% Ethylene Glycol
Water Concentration.

(4)

Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.

(5)

For minimum system volume calculations refer to

Design Features & Information

, on page 15.