Ultima compact freecool chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual

Page 48: Electrical data

Advertising
background image

ULTIMA COMPACT FREECOOL

Chillers

48

Chillers

Technical Manual : 6259576 V1.2.0_02__2013

General Specification

ELECTRICAL DATA

UCFC180D-6/2

UCFC200D-6/2

UCFC225D-6/2

UCFC250D-8/2

UCFC275D-8/2

Unit Data

(1)

Nominal Run Amps

A

109

121

131

146

160

Maximum Start Amps

A

297

358

368

383

440

Rec Mains Fuse Size

A

160

160

200

200

200

Mains Supply

VAC

400V / 3PH / 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Permanent Supply

VAC

230V / 1PH + N / 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Immersion Heater Rating

W

100

100

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Fan & Motor - Per Fan

Quantity

6

6

6

8

8

Full Load Amps

A

1.75

1.75

1.75

1.75

1.75

Locked Rotor Amps

A

6.20

6.20

6.20

6.20

6.20

Motor Size

kW

0.98

0.98

0.98

0.98

0.98

Compressor - Per
Compressor

(1)

Quantity

2 + 2

2 + 2

2 + 2

4

2 + 2

Motor Size

kW

15.0 / 11.7

18.2 / 11.7

18.2 / 15.0

18.2

22.8 / 18.2

Nominal Run Amps

A

27.0 / 22.0

33.0 / 22.0

33.0 / 27.0

33.0

40.0 / 33.0

Oil Heater Rating

W

130.0 / 75.0

130.0 / 75.0

130.0 / 130.0

130.0

130.0 / 130.0

Start Amps

(2)

A

215.0 / 175.0

270.0 / 175.0

270.0 / 215.0

270.0

320.0 / 270.0

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

(1)

Nominal Run Amps

A

99

111

119

134

146

Maximum Start Amps

(2)

A

290

351

359

374

430

Recommended Mains Fuse

A

125

160

160

200

200

Compressor Nominal Run
Amps - Per Compressor

A

2 x 24/2 x 20

2 x 30/2 x 20

2 x 30/2 x 24

4 x 30

2 x 36 / 2 x 30

Electronic Soft-Start

(1)

Nominal Run Amps

A

109

121

131

146

160

Maximum Start Amps

(2)

A

211

250

260

275

312

Recommended Mains Fuse

A

160

160

200

200

200

Water Pump

(1)

Single Head or Run/Standby
- Standard

Unit Nominal Run Amps

A

123

135

145

161

174

Recommended Mains Fuse

A

160

200

200

200

250

Motor Size

kW

7.5

7.5

7.5

7.5

7.5

Full Load Amps

A

14.7

14.7

14.7

14.7

14.7

Single Head or Run/Standby
-Larger

Unit Nominal Run Amps

A

130

142

152

167

181

Recommended Mains Fuse

A

160

200

200

200

250

Motor Size

kW

11

11

11

11

11

Full Load Amps

A

21.4

21.4

21.4

21.4

21.4

Twin Head - Standard

Unit Nominal Run Amps

A

123

135

145

161

174

Recommended Mains Fuse

A

160

200

200

200

250

Motor Size

kW

7.5

7.5

7.5

7.5

7.5

Full Load Amps

A

14.7

14.7

14.7

14.7

14.7

Twin Head - Larger

Unit Nominal Run Amps

A

130

142

152

167

181

Recommended Mains Fuse

A

160

200

200

200

250

Motor Size

kW

11

11

11

11

11

Full Load Amps

A

21.4

21.4

21.4

21.4

21.4

(1)

Based at 12/7°C water and 30°C ambient with standard ac type fans.

(2)

Starting amps refers to the Star connection only with standard ac type fans.