Unit lifting, Ultima compact freecool chillers, Installation data – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 56
ULTIMA COMPACT FREECOOL
Chillers
56
Chillers
Technical Manual : 6259576 V1.2.0_02__2013
Installation Data
UNIT LIFTING
Employ lifting specialists
Local codes and regulations relating to the lifting of this type of equipment should
be observed
Use the appropriate spreader bars/lifting slings (provided by others) with the
holes/lugs provided
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit
IMPORTANT
Do not use 1 chain between 2 lifting points to avoid load shift.
Only use lifting points provided.
Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage
Lift the unit slowly and evenly
IMPORTANT
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.
LIFTING DIMENSIONS
E
D
A
C
B
A
B
C
D
E
2 FANS /1 Row
mm
290
1900
585
2500
1450
3 FANS /1 Row
mm
290
2015
1320
2500
1450
4 FANS /1 Row
mm
290
2870
1315
3000
1450
6 FANS /2 Rows
mm
465
2195
1140
2500
2350
8 FANS /2 Rows
mm
465
2560
1625
2500
2350
10 FANS /2 Rows
mm
465
3135
1900
3500
2350
12 FANS /2 Rows
mm
465
3610
2275
3500
2350
14 FANS /2 Rows
mm
465
4385
2350
4000
2350
16 FANS /2 Rows
mm
465
5035
2550
5000
2350